Chapter 7 Optional Accessories
MS300
(High Speed Model)
7-20
Installation
During installation, please pass the cable through at least one zero-phase reactor.
Use a suitable cable type (insulation class and wire section) so that the cable passes easily through the
zero-phase reactor. Do not pass the grounding cable through zero-phase reactor; only pass the motor
wire through.
With longer motor cables the zero-phase reactor can effectively reduce interference at the motor
output. Install the zero-phase reactor as close to the output of the drive as possible. Figure A is the
installation diagram of a single turn zero-phase reactor. If the diameter allows several turns, the
installation of a multi-turn zero-phase reactor is as shown in Figure B. The more turns, the better the noise
suppression effect.
Figure A
:
Single turn wiring diagram of a shieling wire with a zero-phase reactor
Power
Supply
Zero Phase Reactor
MOTOR
U/T1
V/T2
W/T3
R/L1
S/L2
T/L3
Figure B: Multi-Turn Zero Phase Reactor
Installation notices
Install the zero-phase reactor at the output terminal of the frequency converter (U.V.W.).
After the zero-phase reactor is installed, the electromagnetic radiation and load stress emitted by the
wiring of the frequency converter is reduced. The number of zero-phase reactor required for the drive
depends on the length of wiring and the voltage of the drive.
The normal operating temperature of the zero-phase reactor should be lower than 85 °C (176 °F).
However, when the zero-phase reactor is saturated, its temperature may exceed 85°C (176 °F). Please
increase the number of zero-phase reactors to avoid saturation. The following are reasons that might
cause saturation of the zero-phase reactors. For example: The wiring of the drive is too long; the drive
has several sets of load; the wiring is in parallel; the drive uses high capacitance wiring. If the
temperature of the zero-phase reactor exceeds 85 °C (176 °F) during the operation of the drive, the
number of the zero-phase reactor should be increased.
Summary of Contents for VFD11AMS21AFSHA
Page 5: ...IV This page intentionally left blank...
Page 8: ...Chapter 1 Introduction MS300 High Speed Model 1 3 1 2 Model Name 1 3 Serial Number...
Page 20: ...Chapter 3 Installation MS300 High Speed Model 3 3...
Page 21: ...Chapter 3 Installation MS300 High Speed Model 3 4 This page intentionally left blank...
Page 24: ...Chapter 4 Wiring MS300 High Speed Model 4 3 4 1 Wiring...
Page 25: ...Chapter 4 Wiring MS300 High Speed Model 4 4 Figure 1...
Page 27: ...Chapter 4 Wiring MS300 High Speed Model 4 6 4 2 System Wiring Diagram...
Page 43: ...Chapter 6 Control Terminals MS300 High Speed Model 6 6 This page intentionally left blank...
Page 91: ...Chapter 8 Optional Cards MS300 High Speed Model 8 8 Frame F Fig 8 16...
Page 115: ...Chapter 9 Specification MS300 High Speed Model 9 10 This page intentionally left blank...
Page 123: ...Chapter 10 Digital Keypad MS300 High Speed Model 10 8 This page intentionally left blank...
Page 293: ...Chapter 13 Warning Codes MS300 High Speed Model 13 6 This page intentionally left blank...
Page 303: ...Chapter 14 Error Codes MS300 High Speed Model 14 10 This page intentionally left blank...