Chapter 8 Optional Cards
MS300
(High Speed Model)
8-10
Environment
Noise immunity
ESD (IEC 61800-5-1, IEC 6100-4-2)
EFT (IEC 61800-5-1, IEC 6100-4-4)
Surge Test
(IEC 61800-5-1,
IEC 6100-4-5)
Conducted Susceptibility Test
(IEC 61800-5-1,
IEC 6100-4-6)
Operation / Storage
Operation
:
-10°C ~ 50°C (temperature)
,
90% (humidity)
Storage
:
-25°C ~ 70°C (temperature)
,
95% (humidity)
Shock / Vibration resistance
International standards
:
IEC 61800-5-1,
IEC 60068-2-6 / IEC 61800-5-1,
IEC 60068-2-27
Communication Parameters for VFD-MS300 Connected to EtherNet
When VFD-MS300 links to EtherNet, please set up the communication parameters based on the table below.
The EtherNet master will be able to read/write frequency command word and operation command word to
VFD-MS300 after the communication parameters are set.
Parameter
Function
Current Set Value
Definition of Parameter Values
00-20
Setting for source of
frequency command
8
The frequency command is controlled by
option card
00-21
Setting for source of
operation command
5
The operation command is controlled by
option card
09-30
Decoding method for
communication
0
Decoding method for Delta AC motor drive
09-75
IP setting
0
Static IP(0) / Dynamic distribution IP(1)
09-76
IP address -1
192
IP address 192.168.1.5
09-77
IP address -2
168
IP address 192.168.1.5
09-78
IP address -3
1
IP address 192.168.1.5
09-79
IP address -4
5
IP address 192.168.1.5
09-80
Netmask -1
255 Netmask
255.255.255.0
09-81
Netmask -2
255 Netmask
255.255.255.0
09-82
Netmask -3
255 Netmask
255.255.255.0
09-83
Netmask -4
0 Netmask
255.255.255.0
09-84
Default gateway -1
192
Default gateway 192.168.1.1
09-85
Default gateway -2
168
Default gateway 192.168.1.1
09-86
Default gateway -3
1
Default gateway 192.168.1.1
09-87
Default gateway -4
1
Default gateway 192.168.1.1
Basic Registers
BR#
R/W
Content
Set Value
#0
R
Model name
Set up by the system. The model code of CMM-MOD01=H’0203
#1 R
Firmware
version
Displaying the current firmware version in hex, e.g. 0100h indicates
firmware version V1.00
#2 R
Release date of the
version
Displaying the data in decimal form. 10,000s digit and 1,000s digit
are for “month”; 100s digit and 10s digit are for “day”.
For 1 digit: 0 = morning; 1 = afternoon
#11
R/W
MODBUS Timeout
Pre-defined setting: 500 (ms)
#13
R/W
Keep Alive Time
Pre-defined setting: 30 (s)
Summary of Contents for VFD11AMS21AFSHA
Page 5: ...IV This page intentionally left blank...
Page 8: ...Chapter 1 Introduction MS300 High Speed Model 1 3 1 2 Model Name 1 3 Serial Number...
Page 20: ...Chapter 3 Installation MS300 High Speed Model 3 3...
Page 21: ...Chapter 3 Installation MS300 High Speed Model 3 4 This page intentionally left blank...
Page 24: ...Chapter 4 Wiring MS300 High Speed Model 4 3 4 1 Wiring...
Page 25: ...Chapter 4 Wiring MS300 High Speed Model 4 4 Figure 1...
Page 27: ...Chapter 4 Wiring MS300 High Speed Model 4 6 4 2 System Wiring Diagram...
Page 43: ...Chapter 6 Control Terminals MS300 High Speed Model 6 6 This page intentionally left blank...
Page 91: ...Chapter 8 Optional Cards MS300 High Speed Model 8 8 Frame F Fig 8 16...
Page 115: ...Chapter 9 Specification MS300 High Speed Model 9 10 This page intentionally left blank...
Page 123: ...Chapter 10 Digital Keypad MS300 High Speed Model 10 8 This page intentionally left blank...
Page 293: ...Chapter 13 Warning Codes MS300 High Speed Model 13 6 This page intentionally left blank...
Page 303: ...Chapter 14 Error Codes MS300 High Speed Model 14 10 This page intentionally left blank...