Chapter 12 Description of Parameter Settings
MS300
(High Speed Model)
12-02-10
bit 0 ~ bit 6 correspond to MI1 ~ MI7 respectively.
bit 0 (MI1) default is FWD terminal, bit 1 (MI2) default is REV terminal. This parameter cannot be
used to change input mode when Pr. 02-00
≠
0.
User can change terminal ON / OFF status by communicating.
For example: MI3 is set to 1 (multi-stage speed command 1), MI4 is set to 2 (multi-stage speed
command 2). Then the f 2
nd
stage speed command = 1001
2
= 9
10
As long as Pr. 02-12 = 9 be set by communication, there is no need to make wiring of any
multi-function terminal to run forward with 2
nd
stage speed.
bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0
MI7 MI6 MI5 MI4 MI3 MI2 MI1
Use Pr. 11-42 bit 1 to select whether FWD / REV terminal is controlled by Pr. 02-12 bit 0 and bit 1.
Multi-function Output 1 (Relay1)
Factory Setting: 11
Multi-function Output 2 (MO1)
Multi-function Output 3 (MO2)
Factory Setting: 0
Settings 0: No function
1: Operation indication
2: Operation speed attained
3: Desired frequency attained 1 (Pr. 02-22)
4: Desired frequency attained 2 (Pr. 02-24)
5: Zero speed (Frequency command)
6: Zero speed, include STOP (Frequency command)
7: Over torque 1 (Pr. 06-06~06-08)
8: Over torque 2 (Pr. 06-09~06-11)
9: Drive is ready
10: Low voltage warning (LV) (Pr. 06-00)
11: Malfunction indication
13: Overheat warning (Pr. 06-15, OH1)
14: Software brake signal indication (Pr. 07-00)
17: Count value attained (Pr. 02-20; not return to 0)
18: Count value attained (Pr. 02-19; returns to 0)
19: External interrupt B.B. input
(
Base Block)
20: Warning output
21: Over voltage warning
22: Over-current stall prevention warning
23: Over-voltage stall prevention warning
24: Operation source
25: Forward command
26: Reverse command
29: Output when frequency
≧
Pr.02-34 (
≧
02-34)
Summary of Contents for VFD11AMS21AFSHA
Page 5: ...IV This page intentionally left blank...
Page 8: ...Chapter 1 Introduction MS300 High Speed Model 1 3 1 2 Model Name 1 3 Serial Number...
Page 20: ...Chapter 3 Installation MS300 High Speed Model 3 3...
Page 21: ...Chapter 3 Installation MS300 High Speed Model 3 4 This page intentionally left blank...
Page 24: ...Chapter 4 Wiring MS300 High Speed Model 4 3 4 1 Wiring...
Page 25: ...Chapter 4 Wiring MS300 High Speed Model 4 4 Figure 1...
Page 27: ...Chapter 4 Wiring MS300 High Speed Model 4 6 4 2 System Wiring Diagram...
Page 43: ...Chapter 6 Control Terminals MS300 High Speed Model 6 6 This page intentionally left blank...
Page 91: ...Chapter 8 Optional Cards MS300 High Speed Model 8 8 Frame F Fig 8 16...
Page 115: ...Chapter 9 Specification MS300 High Speed Model 9 10 This page intentionally left blank...
Page 123: ...Chapter 10 Digital Keypad MS300 High Speed Model 10 8 This page intentionally left blank...
Page 293: ...Chapter 13 Warning Codes MS300 High Speed Model 13 6 This page intentionally left blank...
Page 303: ...Chapter 14 Error Codes MS300 High Speed Model 14 10 This page intentionally left blank...