Chapter 12 Description of Parameter Settings
MS300
(High Speed Model)
12-09-1
09 Communication Parameters
The parameter can be set during the operation.
Pin 1~2,7,8: Reserv ed
Pin 3, 6: GND
Pin 4: SG-
Pin 5: SG+
RS-485
8
1
Modbus RS- 485
When us ing communication devi ces,
connects AC dr ive with P C by us ing
Delta IFD6530 or IFD6500.
Communication Address
Factory Setting: 1
Settings 1~254
If the AC motor drive is controlled by RS-485 serial communication, the communication address
for this drive must be set via this parameter and each AC motor drive’s communication address
must be different.
COM1 Transmission Speed
Factory Setting: 9.6
Settings 4.8~115.2 Kbps
This parameter is for setting up the transmission speed of computer and the drive.
Please set 4.8 Kbps, 9.6 Kbps, 19.2 Kbps, 38.4 Kbps, 57.6 Kbps, or 115.2 Kbps. Otherwise the
transmission speed will be replaced by 9.6 Kbps.
COM1 Transmission Fault Treatment
Factory Setting: 3
Settings 0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning and continue operation
This parameter is to set the reaction of MODBUS transmission errors with the host. Detection
time can be set in Pr. 09-03.
COM1 Time-out Detection
Factory Setting: 0.0
Settings 0.0~100.0 sec.
It is used to set the communication transmission time-out.
COM1 Communication Protocol
Factory Setting: 1
Settings 1: 7N2 (ASCII)
2: 7E1 (ASCII)
3: 7O1 (ASCII)
4: 7E2 (ASCII)
5: 7O2 (ASCII)
6: 8N1 (ASCII)
7: 8N2 (ASCII)
8: 8E1 (ASCII)
MODBUS RS-485
Summary of Contents for VFD11AMS21AFSHA
Page 5: ...IV This page intentionally left blank...
Page 8: ...Chapter 1 Introduction MS300 High Speed Model 1 3 1 2 Model Name 1 3 Serial Number...
Page 20: ...Chapter 3 Installation MS300 High Speed Model 3 3...
Page 21: ...Chapter 3 Installation MS300 High Speed Model 3 4 This page intentionally left blank...
Page 24: ...Chapter 4 Wiring MS300 High Speed Model 4 3 4 1 Wiring...
Page 25: ...Chapter 4 Wiring MS300 High Speed Model 4 4 Figure 1...
Page 27: ...Chapter 4 Wiring MS300 High Speed Model 4 6 4 2 System Wiring Diagram...
Page 43: ...Chapter 6 Control Terminals MS300 High Speed Model 6 6 This page intentionally left blank...
Page 91: ...Chapter 8 Optional Cards MS300 High Speed Model 8 8 Frame F Fig 8 16...
Page 115: ...Chapter 9 Specification MS300 High Speed Model 9 10 This page intentionally left blank...
Page 123: ...Chapter 10 Digital Keypad MS300 High Speed Model 10 8 This page intentionally left blank...
Page 293: ...Chapter 13 Warning Codes MS300 High Speed Model 13 6 This page intentionally left blank...
Page 303: ...Chapter 14 Error Codes MS300 High Speed Model 14 10 This page intentionally left blank...