Chapter 12 Description of Parameter Settings
MS300
(High Speed Model)
12-06-22
Software Detection GFF Current Level
Factory Setting: 60.0
Settings 0.0~6553.5 %
Software Detection GFF Filter Time
Factory Setting: 0.10
Settings 0.00~655.35 sec.
When the drive detects the unbalanced three-phase output current is higher than the setting of
Pr. 06-60, GFF protection will be activated. Then the drive will stop outputting.
Operation Time of Fault Record 1 (Day)
Operation Time of Fault Record 2 (Day)
Operation Time of Fault Record 3 (Day)
Operation Time of Fault Record 4 (Day)
Operation Time of Fault Record 5 (Day)
Operation Time of Fault Record 6 (Day)
Factory Setting: Read only
Settings 0~65535 days
Operation Time of Fault Record 1 (Min.)
Operation Time of Fault Record 2 (Min.)
Operation Time of Fault Record 3 (Min.)
Operation of Fault Record 4 (Min.)
Operation of Fault Record 5 (Min.)
Operation of Fault Record 6 (Min.)
Factory Setting: Read only
Settings 0~1439 min.
If there is any malfunction when the drive operating, Pr. 06-17~06-22 will record malfunctions,
and Pr. 06-63~06-70 can record the operation time for 4 malfunctions in sequence. It can help to
check if there is any problem with the drive according to the spacing of fault time recorded.
For example: The 1
st
error: ocA occurs after motor drive operates for 1000 minutes.
The 2
nd
error: ocd occurs after another 1000 minutes.
The 3
rd
error: ocn occurs after another 1000 minutes.
The 4
th
error: ocA occurs after another 1000 minutes.
The 5
th
error: ocd occurs after another 1000 minutes.
The 6
th
error: ocn occurs after another 1000 minutes.
Then Pr. 06-17~06-22 and Pr. 06-63~06-70 recorded as follows:
Parameter record method as follows:
1
st
fault
2
nd
fault
3
rd
fault
4
th
fault
5
th
fault
6
th
fault
06-17
ocA ocd ocn ocA ocd ocn
06-18
0 ocA ocd ocn ocA ocd
06-19
0 0 ocA ocd ocn ocA
06-20 0
0
0
ocA ocd
ocn
06-21
0 0 0 0
ocA
ocd
06-22
0 0 0 0 0
ocA
Summary of Contents for VFD11AMS21AFSHA
Page 5: ...IV This page intentionally left blank...
Page 8: ...Chapter 1 Introduction MS300 High Speed Model 1 3 1 2 Model Name 1 3 Serial Number...
Page 20: ...Chapter 3 Installation MS300 High Speed Model 3 3...
Page 21: ...Chapter 3 Installation MS300 High Speed Model 3 4 This page intentionally left blank...
Page 24: ...Chapter 4 Wiring MS300 High Speed Model 4 3 4 1 Wiring...
Page 25: ...Chapter 4 Wiring MS300 High Speed Model 4 4 Figure 1...
Page 27: ...Chapter 4 Wiring MS300 High Speed Model 4 6 4 2 System Wiring Diagram...
Page 43: ...Chapter 6 Control Terminals MS300 High Speed Model 6 6 This page intentionally left blank...
Page 91: ...Chapter 8 Optional Cards MS300 High Speed Model 8 8 Frame F Fig 8 16...
Page 115: ...Chapter 9 Specification MS300 High Speed Model 9 10 This page intentionally left blank...
Page 123: ...Chapter 10 Digital Keypad MS300 High Speed Model 10 8 This page intentionally left blank...
Page 293: ...Chapter 13 Warning Codes MS300 High Speed Model 13 6 This page intentionally left blank...
Page 303: ...Chapter 14 Error Codes MS300 High Speed Model 14 10 This page intentionally left blank...