Chapter 12 Description of Parameter Settings
MS300
(High Speed Model)
12-03-18
ACI Proportional Highest Point
Factory Setting: 100.00
Settings 0.00~100.00 %
When Pr. 03-29 = 1, ACI setting is 0-10 V and the unit is in voltage (V).
When Pr. 03-29
≠
1, ACI setting is 0-20 mA or 4-20 mA and the unit is in current (mA).
When setting analog input ACI to frequency command, it 100 % corresponds to Fmax (Pr. 01-00
Max. operation frequency).
The 3 parameters (Pr. 03-57, Pr. 03-59 and Pr. 03-61) must meet the following argument:
Pr. 03-57 < Pr. 03-59 < Pr. 03-61. The 3 proportional points (Pr. 03-58, Pr. 03-60 and Pr. 03-62)
doesn’t have any limit. Between two points is a linear calculation.
The output % will become 0 % when the ACI input value is lower than low point setting.
For example:
If Pr. 03-57 = 2 mA; Pr. 03-58 = 10 %, then the output will become 0 % when AVI input is
≤
2 mA.
If the ACI input is swing between 2 mA and 2.1 mA, drive’s output frequency will beats between 0
% and 10 %.
AVI Voltage Lowest Point
Factory Setting: 0.00
Settings 0.00~10.00 V
AVI Voltage Proportional Lowest Point
Factory Setting: 0.00
Settings -100.00~100.00 %
AVI Voltage Mid-point
Factory Setting: 5.00
Settings 0.00~10.00 V
AVI Voltage Proportional Mid-point
Factory Setting: 50.00
Settings -100.00~100.00 %
AVI Voltage Highest Point
Factory Setting: 10.00
Settings 0.00~10.00 V
AVI Voltage Proportional Highest Point
Factory Setting: 100.00
Settings -100.00~100.00 %
When setting positive voltage AVI to frequency command, it 100 % corresponds to Fmax
(Pr. 01-00 Max. operation frequency) and the motor runs in forward direction.
The 3 parameters (Pr. 03-63, Pr. 03-65 and Pr. 03-67) must meet the following argument:
Pr. 03-63 < Pr. 03-65 < Pr. 03-67. The 3 proportional points (Pr. 03-54, Pr. 03-66 and Pr. 03-68)
doesn’t have any limit. Between two points is a linear calculation.
The output % will become 0 % when positive voltage AVI input value is lower than low point
setting.
Summary of Contents for VFD11AMS21AFSHA
Page 5: ...IV This page intentionally left blank...
Page 8: ...Chapter 1 Introduction MS300 High Speed Model 1 3 1 2 Model Name 1 3 Serial Number...
Page 20: ...Chapter 3 Installation MS300 High Speed Model 3 3...
Page 21: ...Chapter 3 Installation MS300 High Speed Model 3 4 This page intentionally left blank...
Page 24: ...Chapter 4 Wiring MS300 High Speed Model 4 3 4 1 Wiring...
Page 25: ...Chapter 4 Wiring MS300 High Speed Model 4 4 Figure 1...
Page 27: ...Chapter 4 Wiring MS300 High Speed Model 4 6 4 2 System Wiring Diagram...
Page 43: ...Chapter 6 Control Terminals MS300 High Speed Model 6 6 This page intentionally left blank...
Page 91: ...Chapter 8 Optional Cards MS300 High Speed Model 8 8 Frame F Fig 8 16...
Page 115: ...Chapter 9 Specification MS300 High Speed Model 9 10 This page intentionally left blank...
Page 123: ...Chapter 10 Digital Keypad MS300 High Speed Model 10 8 This page intentionally left blank...
Page 293: ...Chapter 13 Warning Codes MS300 High Speed Model 13 6 This page intentionally left blank...
Page 303: ...Chapter 14 Error Codes MS300 High Speed Model 14 10 This page intentionally left blank...