Chapter 6 Control Terminals
MS300
(High Speed Model)
6-4
Terminals
Terminal Function
Factory Setting (NPN mode)
RA
Multi-function relay output 1
(Relay N.O. a)
Programmable relay output, see Pr. 02-13.
Resistive Load
3 A (N.O.) / 3 A (N.C.) 250 VAC
5 A (N.O.) / 3 A (N.C.) 30 VDC
Inductive Load (COS 0.4)
1.2 A (N.O.)/ 1.2 A (N.C.) 250 VAC
2.0 A (N.O.)/ 1.2 A (N.C.) 30 VDC
Various kinds of monitor signals output, e.g.: operation,
frequency attained, overload indication etc..
RB
Multi-function relay output 1
(Relay N.C. b)
RC
Multi-function relay common
(Relay)
+10V
Potentiometer power supply
+10.5 ± 0.5 VDC / 20 mA
AVI
Analog voltage input
internal circuit
internal circuit
Programmable analog input, see Pr. 03-00
Impedance: 20 k
Ω
Range 0~Max. Output Frequency (Pr. 01-00):
0 ~ +10 V / -10 ~ +10 V
Range switching by Pr. 03-00 , Pr. 03-28
ACI
Analog current input
ACM
ACI
ACI circuit
internal circuit
Programmable analog input, see Pr. 03-01
Impedance: 250
Ω
Range 0~ Max. Output Frequency (Pr. 01-00):
0~20 mA / 4~20 mA / 0~10 V
Range switching by Pr. 03-01 , Pr. 03-29
AFM
Multi-function analog voltage
output
Switch: the factory setting of AFM is 0~10 V (Voltage
mode), use the switch and Pr. 03-31 to change to
current mode (0~20 mA / 4 mA~20 mA). Must follow the
indication on the back side of front cover or page 6-1 of
user manual when using the switch.
Voltage mode
Range: 0~10 V (Pr. 03-31=0) corresponding to the max.
operating range of the control object
Max. output current: 2 mA
Max. Load: 5 k
Ω
Current mode
Range: 0~20 mA (Pr. 03-31=1) / 4 mA~20 mA
(Pr. 03-31=2) corresponding to the max.
operating range of the control object
Max. load: 500
Ω
ACM
Analog Signal Common
Common for analog terminals
Summary of Contents for VFD11AMS21AFSHA
Page 5: ...IV This page intentionally left blank...
Page 8: ...Chapter 1 Introduction MS300 High Speed Model 1 3 1 2 Model Name 1 3 Serial Number...
Page 20: ...Chapter 3 Installation MS300 High Speed Model 3 3...
Page 21: ...Chapter 3 Installation MS300 High Speed Model 3 4 This page intentionally left blank...
Page 24: ...Chapter 4 Wiring MS300 High Speed Model 4 3 4 1 Wiring...
Page 25: ...Chapter 4 Wiring MS300 High Speed Model 4 4 Figure 1...
Page 27: ...Chapter 4 Wiring MS300 High Speed Model 4 6 4 2 System Wiring Diagram...
Page 43: ...Chapter 6 Control Terminals MS300 High Speed Model 6 6 This page intentionally left blank...
Page 91: ...Chapter 8 Optional Cards MS300 High Speed Model 8 8 Frame F Fig 8 16...
Page 115: ...Chapter 9 Specification MS300 High Speed Model 9 10 This page intentionally left blank...
Page 123: ...Chapter 10 Digital Keypad MS300 High Speed Model 10 8 This page intentionally left blank...
Page 293: ...Chapter 13 Warning Codes MS300 High Speed Model 13 6 This page intentionally left blank...
Page 303: ...Chapter 14 Error Codes MS300 High Speed Model 14 10 This page intentionally left blank...