Chapter 12 Description of Parameter Settings
MS300
(High Speed Model)
12-06-6
When Pr. 06-06 or Pr. 06-09 is set to 2 or 4,
there will be ot1 / ot2 warning displayed and the drive
will stop running after over-torque detection. The drive will keep running after manually reset.
ON
Ove r-t orque det ect ion leve l
06-07 (06-10)
Out put current
Multi-fu nct ion outpu t
terminal=7 or 8
O ver-torqu e dete ction time
06-08 (06-11)
Manually reset
Electronic Thermal Relay Selection 1 (Motor 1)
Electronic Thermal Relay Selection 2 (Motor 2)
Factory Setting: 2
Settings 0: Inverter motor (with external forced cooling)
1: Standard motor (motor with fan on the shaft)
2: Disable
It is used to prevent self-cooled motor overheats under low speed. User can use electronic
thermal relay to limit the output power of drive.
Setting as 0 is suitable for Inverter motor (motor fan using independent power supply). For this
kind of motor, there is no significant
correlation between cooling capacity and motor speed.
Therefore the action of electronic thermal relay will remain stable in low speed to ensure the load
capability of motor in low speed.
Setting as 1 is suitable for standard motor (motor fan is fixed on the rotor shaft). For this kind of
motor, the cooling capacity is lower in low speed. Therefore the action of electronic thermal relay
will reduce the action time to ensure the life of motor.
When the power ON / OFF is switched frequently, if the power is switched OFF, the electronic
thermal relay protection will be reset. Therefore even setting as 0 or 1 may not protect the motor
well. If there are several motors connected to one drive, please install electronic thermal relay in
each motor respectively.
Electronic Thermal Relay Action Time 1 (Motor 1)
Electronic Thermal Relay Action Time 2 (Motor 2)
Factory Setting: 60.0
Settings 30.0~600.0 sec.
The parameter is set by 150 % of motor rated current and used with the setting of Pr. 06-14 and
Pr. 06-28 to prevent the motor from damage due to overheating. When it reaches the setting, the
drive will display “EoL1 / EoL2”, and the motor will be free running to stop.
Summary of Contents for VFD11AMS21AFSHA
Page 5: ...IV This page intentionally left blank...
Page 8: ...Chapter 1 Introduction MS300 High Speed Model 1 3 1 2 Model Name 1 3 Serial Number...
Page 20: ...Chapter 3 Installation MS300 High Speed Model 3 3...
Page 21: ...Chapter 3 Installation MS300 High Speed Model 3 4 This page intentionally left blank...
Page 24: ...Chapter 4 Wiring MS300 High Speed Model 4 3 4 1 Wiring...
Page 25: ...Chapter 4 Wiring MS300 High Speed Model 4 4 Figure 1...
Page 27: ...Chapter 4 Wiring MS300 High Speed Model 4 6 4 2 System Wiring Diagram...
Page 43: ...Chapter 6 Control Terminals MS300 High Speed Model 6 6 This page intentionally left blank...
Page 91: ...Chapter 8 Optional Cards MS300 High Speed Model 8 8 Frame F Fig 8 16...
Page 115: ...Chapter 9 Specification MS300 High Speed Model 9 10 This page intentionally left blank...
Page 123: ...Chapter 10 Digital Keypad MS300 High Speed Model 10 8 This page intentionally left blank...
Page 293: ...Chapter 13 Warning Codes MS300 High Speed Model 13 6 This page intentionally left blank...
Page 303: ...Chapter 14 Error Codes MS300 High Speed Model 14 10 This page intentionally left blank...