Chapter 11 Summary of Parameter Settings
MS300
(High Speed Model)
11-24
Pr.
Explanation
Settings
Factory
Setting
06-42 Drive’s status at malfunction
0000h~FFFFh
Read
only
06-44 STO latch selection
0: STO Latch
1: STO No Latch
0
06-45
Treatment to output phase loss
detection (OPHL)
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
3
06-46 Detection time of output phase loss
0.000~65.535 sec.
0.500
06-47
Current detection level of output
phase loss
0.00~100.00 %
1.00
06-48 DC Brake time of output phase loss
0.000~65.535 sec.
0.000
06-49 LvX auto reset
0: Disabled
1: Enabled
0
06-53
Treatment for the detected input
phase Loss (OrP)
0: Warn and ramp to stop
1: Warn and coast to stop
0
06-55 Derating
protection
0: Constant rated current and limit carrier wave by
load current and temperature
1: Constant carrier frequency and limit load current
by setting carrier wave
2: Constant rated current (same as setting 0), but
close current limit
0
06-56 PT100 voltage level 1
0.000~10.000 V
5.000
06-57 PT100 voltage level 2
0.000~10.000 V
7.000
06-58 PT100 level 1 frequency protect
0.0~1500.0 Hz
0.0
06-59
Delay Time of Activating PT100
Level 1 Frequency Protection
0~6000 sec.
60
06-60
Software detection GFF current
level
0.0~6553.5 %
60.0
06-61 Software detection GFF filter time
0.00~655.35 sec.
0.10
06-63
Operation time of fault record 1
(Day)
0~65535 days
Read
only
06-64
Operation time of fault record 1
(Min.)
0~1439 min.
Read
only
06-65
Operation time of fault record 2
(Day)
0~65535 days
Read
only
06-66
Operation time of fault record 2
(Min.)
0~1439 min.
Read
only
Summary of Contents for VFD11AMS21AFSHA
Page 5: ...IV This page intentionally left blank...
Page 8: ...Chapter 1 Introduction MS300 High Speed Model 1 3 1 2 Model Name 1 3 Serial Number...
Page 20: ...Chapter 3 Installation MS300 High Speed Model 3 3...
Page 21: ...Chapter 3 Installation MS300 High Speed Model 3 4 This page intentionally left blank...
Page 24: ...Chapter 4 Wiring MS300 High Speed Model 4 3 4 1 Wiring...
Page 25: ...Chapter 4 Wiring MS300 High Speed Model 4 4 Figure 1...
Page 27: ...Chapter 4 Wiring MS300 High Speed Model 4 6 4 2 System Wiring Diagram...
Page 43: ...Chapter 6 Control Terminals MS300 High Speed Model 6 6 This page intentionally left blank...
Page 91: ...Chapter 8 Optional Cards MS300 High Speed Model 8 8 Frame F Fig 8 16...
Page 115: ...Chapter 9 Specification MS300 High Speed Model 9 10 This page intentionally left blank...
Page 123: ...Chapter 10 Digital Keypad MS300 High Speed Model 10 8 This page intentionally left blank...
Page 293: ...Chapter 13 Warning Codes MS300 High Speed Model 13 6 This page intentionally left blank...
Page 303: ...Chapter 14 Error Codes MS300 High Speed Model 14 10 This page intentionally left blank...