PowerVault ML6000 Maintenance Guide
421
•
T022
on page 220
•
T023
on page 221
Problem: A problem has been detected and isolated to a drive sled. A drive sled replacement is required.
1
Make note of the part number on the rear of the drive sled, and contact Service for a drive sled
replacement.
2
When the new drive sled is available, use the
Operations > Change Drive Mode
menu on the local
display, or the
Operations > Drives > Change Mode
menu on the remote user interface to take the
drive sled offline.
When the blue LED on the rear of the drive sled is lit solid, the drive sled is ready to be removed.
3
Insert the new drive sled and wait for the drive sled firmware to load. The drive sled’s green LED will
blink for 3 seconds on, followed by two short blinks while firmware is loaded.
4
Use the
Operations > Change Drive Mode
menu on the local display or the
Operations > Drives >
Change Mode
menu on the remote user interface to take the drive sled online.
5
You have three options:
a. Select
Close
to close the ticket now.
b. Select
Exit
to leave the ticket open for future troubleshooting.
c. Select
Back
to return to the Diagnostic Resolution.
RR002 - Remove and Replace LCB
This RR provides resolution steps for
T064
on page 262.
Problem: A problem has been detected and isolated to the Library Control Blade. The nature of the problem
indicates that replacement may be required.
1
Remove the drives in the Control Module and check the cable connections to the board behind the lower
drive. If they are loose, firmly push them back into place, and close this ticket. If this problem occurs
again, proceed with the following step.
2
If both this ticket and a T067 - Display Assembly Hardware Failure are generated within a few minutes
of each other, the problem lies with one of the power supplies in the Control Module. Contact Service
for replacement of a Power Supply. Otherwise, proceed with the following steps.
3
Contact Service to order an LCB.
4
Save the library configuration via the
Tools > Save/Restore
menu selection.
5
When the new LCB is received, follow the instructions delivered in the package.
Your original compact flash file system should allow the new LCB to immediately recognize your library
and be operational.
The saved configuration is only necessary if there are additional problems with your compact flash.
6
If this problem persists after replacing the LCB, the problem may lie with the display. Contact Service
to replace the display assembly.
7
You have three options:
a. Select
Close
to close the ticket now.
b. Select
Exit
to leave the ticket open for future troubleshooting.
c. Select
Back
to return to the Diagnostic Resolution.
Summary of Contents for PowerVault ML6000
Page 1: ...w w w d e l l c o m s u p p o r t d e l l c o m MaintenanceGuide Dell PowerVault ML6000 ...
Page 14: ...xiv Tables ...
Page 18: ...xviii Figures ...
Page 452: ...434 Troubleshooting the Tape Library ...
Page 456: ...438 Library Drawings Library Rear View Figure 32 ML6020 Rear View ...
Page 468: ...450 Library Drawings Power Supplies Figure 49 Power Supplies ...
Page 477: ...PowerVault ML6000 Maintenance Guide 459 Figure 58 Electrical System 5U Library Control Module ...
Page 478: ...460 Library Drawings Figure 59 LCB Functions ...
Page 479: ...PowerVault ML6000 Maintenance Guide 461 ...
Page 482: ...464 Library Drawings Figure 64 Fan Control Board ...
Page 483: ...PowerVault ML6000 Maintenance Guide 465 Figure 65 Library Cables ...
Page 484: ...466 Library Drawings Figure 66 Library System Grounding ...
Page 485: ...PowerVault ML6000 Maintenance Guide 467 Figure 67 Library Power System ...
Page 486: ...468 Library Drawings ...
Page 494: ...476 Glossary Y axis Y position The vertical position of the library s robotic arm ...