PowerVault ML6000 Maintenance Guide
393
4
You have three options:
a. Select
Close
to close the ticket now.
b. Select
Exit
to leave the ticket open for future troubleshooting.
c. Select
Back
to return to the Diagnostic Resolution.
DR056 - Resolve Module Communication
This DR provides customer resolution steps for
T096
on page 297.
Problem: The library has encountered an error when trying to communicate with its modules.
1
Turn off the library.
2
Remove both the top and bottom terminators and carefully inspect them for bent pins. If any are found,
contact Service for replacement.
3
Remove all module-to-module connectors and carefully inspect them for bent pins. If any are found,
contact Service for replacements.
4
If no bent pins are found on any of these parts, contact Service for further assistance.
5
You have three options:
a. Select
Close
to close the ticket now.
b. Select
Exit
to leave the ticket open for future troubleshooting.
c. Select
Back
to return to the Diagnostic Resolution.
DR057 - Resolve Noisy Fibre Channel Link
This DR provides customer resolution steps for
T097
on page 298.
Problem: The FC I/O blade has detected excessive noise on a specific Fibre Channel port. This includes,
but is not limited to, abnormal communication retries and data errors.
1
Ensure that the fiber cables are properly connected to both the host and the FC I/O blade.
2
Check the fiber cable for any damage or debris in the connectors.
3
Reset the port on the FC I/O blade via the local or remote user interface.
4
If the problem still persists, contact Service for further assistance in resolving the issue.
5
You have three options:
a. Select
Close
to close the ticket now.
b. Select
Exit
to leave the ticket open for future troubleshooting.
c. Select
Back
to return to the Diagnostic Resolution.
DR058 - Resolve Data Path Failure
This DR provides customer resolution steps for
T098
on page 299.
Problem: The FC I/O blade has detected a communication error with the target drive. The drive does not
respond to commands and may no longer be connected.
1
Ensure that the fiber cables are properly connected to both the FC I/O blade and the drive.
2
Check the fiber cable for any damage or debris in the connectors.
3
Reset the port on the FC I/O blade via the local or remote user interface.
Summary of Contents for PowerVault ML6000
Page 1: ...w w w d e l l c o m s u p p o r t d e l l c o m MaintenanceGuide Dell PowerVault ML6000 ...
Page 14: ...xiv Tables ...
Page 18: ...xviii Figures ...
Page 452: ...434 Troubleshooting the Tape Library ...
Page 456: ...438 Library Drawings Library Rear View Figure 32 ML6020 Rear View ...
Page 468: ...450 Library Drawings Power Supplies Figure 49 Power Supplies ...
Page 477: ...PowerVault ML6000 Maintenance Guide 459 Figure 58 Electrical System 5U Library Control Module ...
Page 478: ...460 Library Drawings Figure 59 LCB Functions ...
Page 479: ...PowerVault ML6000 Maintenance Guide 461 ...
Page 482: ...464 Library Drawings Figure 64 Fan Control Board ...
Page 483: ...PowerVault ML6000 Maintenance Guide 465 Figure 65 Library Cables ...