AC line supply 3 x 525-690 V
According to international requirements
VLT type 5042
5052
5062
5072
5102
Normal overload torque (110 %):
Output current
I
VLT,N
[A] (525-550 V) 56
76
90
113
137
I
VLT, MAX
(60 s) [A] (525-550
V)
62
84
99
124
151
I
VLT,N
[A] (551-690 V) 54
73
86
108
131
I
VLT, MAX
(60 s) [A] (551-690
V)
59
80
95
119
144
Output
S
VLT,N
[kVA] (550 V) 53
72
86
108
131
S
VLT,N
[kVA] (575 V) 54
73
86
108
130
S
VLT,N
[kVA] (690 V) 65
87
103
129
157
Typical shaft output
[kW] (550 V) 37
45
55
75
90
[HP] (575 V) 50
60
75
100
125
[kW] (690 V) 45
55
75
90
110
High overload torque (160 %):
Output current
I
VLT,N
[A] (525-550 V) 48
56
76
90
113
I
VLT, MAX
(60 s) [A] (525-550
V)
77
90
122
135
170
I
VLT,N
[A] (551-690 V) 46
54
73
86
108
I
VLT, MAX
(60 s) [A] (551-690
V)
74
86
117
129
162
Output
S
VLT,N
[kVA] (550 V) 46
53
72
86
108
S
VLT,N
[kVA] (575 V) 46
54
73
86
108
S
VLT,N
[kVA] (690 V) 55
65
87
103
129
Typical shaft output
[kW] (550 V) 30
37
45
55
75
[HP] (575 V) 40
50
60
75
100
[kW] (690 V) 37
45
55
75
90
Max. cable cross-section
to motor
[mm
2
]
4,6
[AWG]
2,4,6
2 x 70
2 x 2/0
Max. cable cross-section
to load sharing and brake
[mm
2
]
4,6
[AWG]
2,4,6
2 x 70
2 x 2/0
Normal overload torque (110 %):
Rated input current
I
L,N
[A] (550 V) 60
77
89
110
130
I
L,N
[A] (575 V) 58
74
85
106
124
I
L,N
[A] (690 V) 58
77
87
109
128
High overload torque (160 %):
Rated input current
I
L,N
[A] (550 V) 53
60
77
89
110
I
L,N
[A] (575 V) 51
58
74
85
106
I
L,N
[A] (690 V) 50
58
77
87
109
Max. cable cross-section
power supply
[mm
2
]
4,6
[AWG]
2,4,6
2 x 70
2 x 2/0
Max. pre-fuses (line) [-]/UL
[A]
1
125
160
200
200
250
Efficiency
3
0.97
0.97
0.98
0.98
0.98
Power loss
Normal overload [W] 1458
1717
1913
2262
2662
High overload [W] 1355
1459
1721
1913
2264
Weight
IP 00 [kg]
82
Weight
IP 21/NEMA 1 [kg]
96
Weight
IP 54/NEMA 12 [kg]
96
Enclosure
IP 00, IP 21/NEMA 1 and IP 54/NEMA 12
1. For type of fuse, see section
Fuses.
2. American Wire Gauge.
3. Measured using 100 ft [30 m] shielded motor cables at rated load and rated frequency.
4. Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminals. Always comply with national and local
regulations on min. cable cross-section.
5. Weight without shipping container.
6. Connection bolt power supply and motor: M10; Brake and load sharing: M8
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
31
Technical data
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......