Compact, AC line supply 3 x 200-240 V
According to international requirements
VLT type
5032
5042
5052
Normal overload torque (110 %):
Output current
I
VLT,N
[A] (200-230 V)
115
143
170
I
VLT, MAX
(60 s) [A] (200-230 V)
127
158
187
I
VLT,N
[A] (231-240 V)
104
130
154
I
VLT, MAX
(60 s) [A] (231-240 V)
115
143
170
Output
S
VLT,N
[kVA] (208 V)
41
52
61
S
VLT,N
[kVA] (230 V)
46
57
68
S
VLT,N
[kVA] (240 V)
43
54
64
Typical shaft output
[HP] (208 V)
40
50
60
Typical shaft output
[kW] (230 V)
30
37
45
High overload torque (160 %):
Output current
I
VLT,N
[A] (200-230 V)
88
115
143
I
VLT, MAX
[A] (200-230 V)
132
173
215
I
VLT,N
[A] (231-240 V)
80
104
130
I
VLT, MAX
[A] (231-240 V)
120
285
195
Output
S
VLT,N
[kVA] (208 V)
32
41
52
S
VLT,N
[kVA] (230 V)
35
46
57
S
VLT,N
[kVA] (240 V)
33
43
54
Typical shaft output
[HP] (208 V)
30
40
50
[kW] (230 V)
22
30
37
Max. cable cross-section to motor
and load sharing
[mm
2
]
4,6
[AWG]
2,4,6
120
300 mcm
Max. cable cross-section to brake
[mm
2
]
4,6
[AWG]
2,4,6
25
4
Normal overload torque (110 %):
Rated input current
I
L,N
[A] (230 V)
101.3
126.6
149.9
Normal overload torque (150 %):
Rated input current
I
L,N
[A] (230 V)
77,9
101,3
126,6
Max. cable cross-section
power supply
[mm
2
]
4,6
[AWG]
2,4,6
120
300 mcm
Min. cable cross-section to motor,
power
supply, brake and load sharing
[mm
2
]
4,6
[AWG]
2,4,6
6
8
Max. pre-fuses (line) [-]/UL
[A]
1
150/15
0
200/200
250/250
Efficiency
3
0,96-0,97
Power loss
Normal overload [W]
1089
1361
1612
High overload [W]
838
1089
1361
Weight
IP 00 [kg]
101
101
101
Weight
IP 20 Nema1 [kg]
101
101
101
Weight
IP 54 Nema12 [kg]
104
104
104
Enclosure
IP 00 / Nema 1 (IP 20) / IP 54
1. For type of fuse, see section
Fuses.
2. American Wire Gauge.
3. Measured using 100 ft [30 m] shielded motor cables at rated load and rated frequency.
4. Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminals. Min. cable cross-section
is the minimum allowed cross-section. Always comply with national and local regulations on min. cable cross-section.
5. Weight without shipping container.
6. Connection stud: M8 Brake: M6.
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
15
Technical data
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......