Two wire start/stop
-
Start/stop using terminal 18.
Parameter 302 =
Start
[1]
-
Quick-stop using terminal 27.
Parameter 304 =
Coasting stop inverted
[0]
Pulse start/stop
-
Stop inverted by means of terminal 16.
Parameter 300 =
Stop inverted
[2]
-
Pulse start using terminal 18.
Parameter 302 =
Pulse start
[2]
-
Jog by means of terminal 29.
Parameter 305 =
Jog
[5]
Setup change
-
Selection of setup using terminals 32 and 33.
Parameter 306 =
Selection of setup, lsb
[10]
Parameter 307 =
Selection of setup, msb
[10]
Parameter 004 =
Multi-setup
[5].
Digital speed up/down
-
Speed up and down using terminals 32 and
33.
Parameter 306 =
Speed up
[9]
Parameter 307 =
Speed down
[9]
Parameter 305 =
Freeze reference
[7].