Select
Process control, closed loop
if the application
has a feedback signal that is not directly related to mo-
tor speed (rpm/Hz), but some other unit, such as tem-
perature, pressure, etc. Set the following parameters
in the order shown:
Process control, closed loop (Process PID):
Parameter:
Setting:
Data value:
100
Configuration
Process control, closed loop
[3]
200
Output frequency range/direction
201
Output frequency low limit
202
Output frequency high limit
203
Reference/feedback range
414
Minimum feedback
Only if [0] or [2] in par. 200
415
Maximum feedback
204
Minimum reference
Only if [0] in par. 203
205
Maximum reference
416
Process units
437
Process PID normal/inverse
438
Process PID anti-windup
439
Process PID start frequency
440
Process PID proportional gain
441
Process PID integration time
442
Process PID differentiation time
443
Process PID diff. gain limit
444
Process PID lowpass filter
Select
Torque control, open loop
if PI control is re-
quired, to change the motor frequency in order to
maintain the torque reference (Nm).
This is relevant for winding and extrusion applications.
Torque control, open loop
, is to be selected if the speed
direction is not to be changed during operation; this
means that either a positive or a negative torque ref-
erence is used at all times.
Set the following parameters in order shown:
Torque control, open loop:
Parameter:
Setting:
Data value:
100
Configuration
Torque control, open loop
[4]
200
Output frequency range/direction
201
Output frequency low limit
202
Output frequency high limit
203
Reference/feedback range
204
Minimum reference
Only if [0] in par. 203
205
Maximum reference
414
Minimum feedback
415
Maximum feedback
433
Torque proportional gain
434
Torque integration time
VLT
®
5000 Series
186
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......