304
Terminal 27, input
(DIGITAL INPUT 27)
Value:
See parameter 300.
Function:
This parameter allows a choice between the different
options on terminal 27.
Functions are shown in the table at the beginning of
the section
Parameters - Inputs and Outputs
.
Maximum frequency for terminal 27 is 5 kHz.
Description of choice:
See parameter 300.
305
Terminal 29, input
(DIGITAL INPUT 29)
Value:
See parameter 300.
Function:
This parameter allows a choice between the different
options on terminal 29. The functions are shown in the
table at the beginning of the section
Parameters - In-
puts and Outputs
.
Maximum frequency for terminal 29 is 65 kHz.
Description of choice:
See parameter 300.
306
Terminal 32, input
(DIGITAL INPUT 32)
Value:
See parameter 300.
Function:
This parameter allows a choice between the different
options on terminal 32. The functions are shown in the
table at the beginning of the section
Parameters - In-
puts and Outputs
.
Maximum frequency for terminal 32 is 65 kHz.
Description of choice:
See parameter 300.
307
Terminal 33, input
(DIGITAL INPUT 33)
Value:
See parameter 300.
Function:
This parameter allows a choice between the different
options on terminal 33. The functions are shown in the
table at the beginning of the section
Parameters - In-
puts and Outputs
.
Maximum frequency for terminal 33 is 65 kHz.
Description of choice:
See parameter 300.
Analog inputs
terminal no.
53(voltage)
54(voltage)
60(current)
parameter
308
311
314
Value:
No operation
(NO OPERATION)
[0]
[0]
[0]
Reference
(REFERENCE)
[1]
[1]
[1]
Feedback signal
(FEEDBACK)
[2]
[2]
Torque limit
(TORQUE LIMIT CTRL)
[3]
[2]
[3]
Thermistor
(THERMISTOR INPUT)
[4]
[3]
Relative reference
(RELATIVE REFERENCE)
[4]
[4]
Max. torque frequency
(MAX. TORQUE FREQ.)
[5]
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
113
Progra
mming
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......