See the dedicated fieldbus manuals for further details.
513
Bus time interval
(BUS TIMEOUT TIME)
Value:
1 - 99 sec.
1 sec.
Function:
This parameter sets the maximum time expected to
pass between the receipt of two consecutive tele-
grams. If this time is exceeded, the serial communica-
tion is assumed to have stopped and the desired
reaction is set in parameter 514.
Description of choice:
Set the desired time.
514
Bus time interval function
(BUS TIMEOUT FUNC)
Value:
Off (OFF)
[0]
Freeze output (FREEZE OUTPUT)
[1]
Stop (STOP)
[2]
Jogging (JOGGING)
[3]
Max. speed (MAX SPEED)
[4]
Stop and trip (STOP AND TRIP)
[5]
Function:
This parameter selects the desired reaction of the ad-
justable frequency drive when the set time for bus
timeout (parameter 513) has been exceeded.
If choices [1] to [5] are activated, relay 01 and relay 04
will be de-activated.
If more time-outs occur at the same time the adjustable
frequency drive will give the following priority to the
time-out function:
1.
Parameter 318
Function after time out
2.
Parameter 346
Function after encoder loss
3.
Parameter 514
Bus time interval function.
Description of choice:
The output frequency of the adjustable frequency drive
can: be frozen at the present value, be frozen at the
reference, go to stop, go to jogging frequency (param-
eter 213), go to max. output frequency (parameter
202) or stop and activate a trip.
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
143
Progra
mming
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......