tion of [Fwd/rev], which is only active in
Local operation.
NOTE
If no external stop function has been se-
lected and the [Stop] key has been selec-
ted as inactive, the motor can be started
and can only be stopped by disconnecting
the voltage to the motor.
Control panel - display read-outs
The display read-out state can be varied - see the list
below - depending on whether the adjustable frequen-
cy drive is in normal operation or is being programmed.
Display mode
In normal operation, up to 4 different operating varia-
bles can be indicated continuously: 1.1 and 1.2 and
1.3 and 2, and in line 4 the present operating status or
alarms and warnings that have arisen.
195NA113.10
VAR 2
SETUP
1
STATUS
VAR 1.1 VAR 1.2 VAR 1.3
Display mode - selection of read-outstate
There are three options in connection with the choice
of read-out state in the Display mode - I, II and III. The
choice of read-out state determines the number of op-
erating variables read out.
Read-out
state:
I:
II:
III:
Line 1
Description for op-
erating variable in
line 2
Data value for 3
operating varia-
bles in line 1
Description for 3
operating varia-
bles in line 1
The table below gives the units linked to the variables
in the first and second line of the display.
Operating variable:
Unit:
Reference
[%]
Reference
[unit]
Feedback
[unit]
Frequency
[Hz]
Frequency x scaling
[-]
Motor current
[A]
Torque
[%]
Power
[kW]
Power
[HP]
Output energy
[kWh]
Motor voltage
[V]
DC-link voltage
[V]
Motor thermal load
[%]
VLT thermal load
[%]
Hours run
[Hours]
Input status, dig. Input
[Binary code]
Input status, analog terminal 53
[V]
Input status, analog terminal 54
[V]
Input status, analog terminal 60
[mA]
Pulse reference
[Hz]
External reference
[%]
Status word
[Hex]
Brake effect/2 min.
[kW]
Brake effect/sec.
[kW]
Heat sink temp.
[ºC]
Alarm word
[Hex]
Control word
[Hex]
Warning word 1
[Hex]
Extended status word
[Hex]
Communication option card warning
[Hex]
RPM
[min
-1
]
RPM x scaling
[ - ]
LCP Display text
[ - ]
Operating variables 1.1 and 1.2 and 1.3 in the first line,
and operating variable 2 in the second line are selec-
ted via parameter 009, 010, 011 and 012.
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
73
O
pera
tio
n o
f th
e VLT
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......