Compact AC line supply 3 x 550-600 V
According to international requirements
VLT type
5150
5200
5250
Max input current 110%
I
L,MAX
[A] (550 V)
196
246
281
I
L,MAX
[A] (575 V)
179
226
270
Max input current 160%
I
L,MAX
[A] (550 V)
147
196
246
I
L,MAX
[A] (575 V)
134
179
226
Max. cross-section of copper cable to power [mm
2
]
2 x 120
2 x 120
2 x 120
Max. cross-section of aluminum cable to power [mm
2
]
2 x 185
2 x185
2 x 185
Max. cross-section of copper cable to power [AWG]
2 x4/0
2 x4/0
2 x4/0
Max. cross-section of aluminum cable to power [AWG]
2 x 300
mcm
2 x 300
mcm
2 x 300
mcm
Min. cable cross-section to motor, brake and load shar-
ing
4)
[mm
2/
AWG]
2) 5)
6/8
6/8
6/8
Max. pre-fuses (line power) [-]/UL
1)
[A]
250
350
400
Integral pre-fuses (softcharge circuit) [-]/UL
6)
[A]
30/30
30/30
30/30
Integral pre-fuses (softcharge resistors) [-]/UL
7)
[A]
12/12
12/12
12/12
Integral pre-fuses (SMPS) [-]/UL
8)
[A]
5
5
5
Efficiency
0.96-0.97
Weight IP 00
[kg]
146
146
146
Weight Nema 1 EB
[kg]
161
161
161
Power loss at max. load [W]
5030
6340
7570
Enclosure
IP 00/Nema 1 (IP 20)
1. For type of fuse, see section
Fuses
.
2. American Wire Gauge.
3. Measured using 100 ft [30 m] shielded motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals. Always comply
with national and local regulations on min. cable cross-section.
5. Connection stud 1 x M8/2 x M8.
6. If UL/cUL is to be complied with, AC Littelfuse type KLK, Danfoss ordering no. 176F1147 must be used.
7. If UL/cUL is to be complied with, DC Littelfuse type KLKD, Danfoss ordering no. 176F1192 must be used.
8. If UL/cUL is to be complied with, Bussmann type KTK-5, Danfoss ordering no. 175L3437 must be used.
VLT
®
5000 Series
30
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......