AC line supply 3 x 525-690 V
According to international requirements
VLT type 5122
5152
5202
5252
5302
5352
Normal overload torque (110 %):
Output current
I
VLT,N
[A] (525-550 V) 162
201
253
303
360
418
I
VLT, MAX
(60 s) [A]
(525-550 V)
178
221
278
333
396
460
I
VLT,N
[A] (551-690 V) 155
192
242
290
344
400
I
VLT, MAX
(60 s) [A]
(551-690 V)
171
211
266
319
378
440
Output
S
VLT,N
[kVA] (550 V) 154
191
241
289
343
398
S
VLT,N
[kVA] (575 V) 154
191
241
289
343
398
S
VLT,N
[kVA] (690 V) 185
229
289
347
411
478
Typical shaft output
[kW] (550 V) 110
132
160
200
250
315
[HP]
(575
V) 150
200
250
300
350
400
[kW] (690 V) 132
160
200
250
315
400
High overload torque (160 %):
Output current
I
VLT,N
[A] (525-550 V) 137
162
201
253
303
360
I
VLT, MAX
(60 s) [A]
(525-550 V)
206
243
302
380
455
540
I
VLT,N
[A] (551-690 V) 131
155
192
242
290
344
I
VLT, MAX
(60 s) [A]
(551-690 V)
197
233
288
363
435
516
Output
S
VLT,N
[kVA] (550 V) 131
154
191
241
289
343
S
VLT,N
[kVA] (575 V) 130
154
191
241
289
343
S
VLT,N
[kVA] (690 V) 157
185
229
289
347
411
Typical shaft output
[kW] (550 V) 90
110
132
160
200
250
[HP]
(575
V) 125
150
200
250
300
350
[kW] (690 V) 110
132
160
200
250
315
Max. cable cross-section
to motor
[mm
2
]
4,6
[AWG]
2,4,6
2 x 70
2 x 2/0
2 x 185
2 x 350 mcm
Max. cable cross-section
to load sharing and brake
[mm
2
]
4,6
[AWG]
2,4,6
2 x 70
2 x 2/0
2 x 185
2 x 350 mcm
Normal overload torque (110 %):
Rated input current
I
L,N
[A] (550 V) 158
198
245
299
355
408
I
L,N
[A] (575 V) 151
189
234
286
339
390
I
L,N
[A] (690 V) 155
197
240
296
352
400
High overload torque (160 %):
Rated input current
I
L,N
[A] (550 V) 130
158
198
245
299
355
I
L,N
[A] (575 V) 124
151
189
234
286
339
I
L,N
[A] (690 V) 128
155
197
240
296
352
Max. cable cross-section
power supply
[mm
2
]
4,6
[AWG]
2,4,6
2 x 70
2 x 2/0
2 x 185
2 x 350 mcm
Max. pre-fuses (line) [-]/
UL
[A]
1
315
350
350
400
500
550
Efficiency
3
0,98
Power loss
Normal overload [W] 3114
3612
4292
5155
5821
6149
High overload [W] 2664
2952
3451
4275
4875
5185
Weight
IP 00 [kg] 82
91
112
123
138
151
Weight
IP 21/NEMA 1 [kg] 96
104
125
136
151
165
Weight
IP 54/NEMA 12 [kg] 96
104
125
136
151
165
Enclosure
IP 00, IP 21/NEMA 1 and IP 54/NEMA 12
1. For type of fuse, see section
Fuses.
2. American Wire Gauge.
3. Measured using 100 ft [30 m] shielded motor cables at rated load and rated frequency.
4. Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminals. Always comply with
national and local regulations on min. cable cross-section.
5. Weight without shipping container.
6. Connection bolt power supply and motor: M10; Brake and load sharing: M8
VLT
®
5000 Series
32
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......