Ambient temperature NEMA 12 (normal overload torque 110%)
Max. 40°C (24-hour average max. 35°C)
Ambient temperature NEMA 1/NEMA 121VLT 5011 500 V
Max. 40°C (24-hour average max. 35°C)
Ambient temperature NEMA 12 VLT 5042-5602, 525-690 V; and
5122-5552, 380-500 V (high overload torque 160%)
Max. 45°C (24-hour average max. 40°C)
Derating for high ambient temperature, see the Design Guide
Min. ambient temperature in full operation
0°C
Min. ambient temperature at reduced performance
-10°C
Temperature during storage/transport
-25 - +65/70°C
Max. altitude above sea level
1000 m
Derating for altitude over 1000 m above sealevel, see the Design Guide
EMC standards applied, Emission
EN 61000-6-3, EN 61000-6-4, EN 61800-3, EN 55011
EMC standards applied, Immunity
EN 61000-6-2, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4
EN 61000-4-5, EN 61000-4-6, VDE 0160/1990.12
VLT 5001-5062, 525 - 600 V do not comply with EMC or Low Voltage Directives.
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
11