Example 2:
External reference signal = 0 V (min) - 10 V (max)
Reference = -50 Hz ccw - 50 Hz cw
Configuration (parameter 100) =Speed control, open
loop.
Setting:
Parameter:
Setting:
Data value:
100
Configuration
Speed control, open loop
[0]
308
Funct. of analog input
Reference
[1]
309
Min. reference signal
Min.
0 V
310
Max. reference signal
Max.
10 V
203
Reference range
Reference range
- Max - + Max [1]
205
Max. reference
100 Hz
214
Reference type
Sum
[0]
215
Preset reference
-50%
200
Output frequency range/direction
Both directions, 0-132 Hz
[1]
The following can be used:
- Catch-up/slow-down via digital input terminals 16,17, 29, 32 or
33
- Freeze reference via digital input terminals 16,17, 29, 32 or 33.