LCP control/as parameter 100
[3] is selected if the ref-
erence is to be set via parameter 003.
LCP digital control/as parameter 100
[4] functions as
LCP control/as parameter 100 [3], although, when pa-
rameter 002 has been set to
Local operation
[1], the
motor may be controlled via the digital inputs in ac-
cordance with the list in section
Shift between local and
remote control
.
NOTE
Shift from Remote control to LCP digital
control and open loop:
The present motor frequency and direction of rotation
must be maintained. If the present direction of rotation
does not correspond to the reversing signal (negative
reference), the motor frequency f
M
will be set at 0 Hz.
Shift from LCP digital control and open loop to Remote
control:
The selected configuration (parameter 100) will be ac-
tive. Shifts are effected without any abrupt movement.
Shift from Remote control to LCP control/as parameter
100 or LCP digital control/as parameter 100.
The present reference will be maintained. If the refer-
ence signal is negative, the local reference will be set
at 0.
Shift from LCP control/as parameter 100 or LCP re-
mote control as parameter 100 to Remote control.
The reference will be replaced by the active reference
signal from the remote control.
014
Local stop
(LOCAL STOP)
Value:
Disable (DISABLE)
[0]
Enable (ENABLE)
[1]
Function:
This parameter disables/enables the local stop func-
tion from the LCP.
This key is used when parameter 002 has been set for
Remote control
[0] or
Local
[1].
Description of choice:
If
Disable
[0] is selected, the [STOP] key will be inac-
tive.
NOTE
If
Enable
is selected, the [STOP] key over-
rules all Start commands.
015
Local jog (LOCAL JOGGING)
Value:
Not possible (DISABLE)
[0]
Possible (ENABLE)
[1]
Function:
This parameter enables/disables the local jog function
on the LCP.
The key is used when parameter 002 has been set for
Remote control [0]
or
Local
[1].
Description of choice:
If
Disable
[0] is selected, the [JOG] key will be inactive.
016
Local reversing
(LOCAL REVERSING)
Value:
Not possible (DISABLE)
[0]
Possible (ENABLE)
[1]
Function:
This parameter enables/disables the reversing func-
tion on the LCP.
This key can only be used if parameter 002 has been
set to
Local operation
[1] and parameter 013 to
LCP
control
[3].
Description of choice:
If
Disable
[0] is selected, the [FWD/REV] key will be
inactive.
See parameter 200.
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
84
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......