Input resistance, R
i
200
Resolution
10 bit + sign
Accuracy on input
Max. error 1% of full scale
Scanning time per input
3 msec.
Terminal no. ground
55
Reliable galvanic isolation: All analog inputs are galvanically isolated from the supply voltage (PELV)* as well as other
inputs and outputs.
* VLT 5001-5062, 525-600 V do not meet PELV.
Control card, pulse/encoder input:
No. of programmable pulse/encoder inputs
4
Terminal nos.
17, 29, 32, 33
Max. frequency on terminal 17
5 kHz
Max. frequency on terminals 29, 32, 33
20 kHz (PNP open collector)
Max. frequency on terminals 29, 32, 33
65 kHz (Push-Pull)
Voltage level
0-24 V DC (PNP positive logics)
Voltage level, logical '0'
< 5 V DC
Voltage level, logical '1'
>10 V DC
Maximum voltage on input
28 V DC
Input resistance, R
i
2 k
Scanning time per input
3 msec.
Resolution
10 bit + sign
Accuracy (100-1 kHz), terminals 17, 29, 33
Max. error: 0.5% of full scale
Accuracy (1-5 kHz), terminal 17
Max. error: 0.1% of full scale
Accuracy (1-65 kHz), terminals 29, 33
Max. error: 0.1% of full scale
Reliable galvanic isolation: All pulse/encoder inputs are galvanically isolated from the supply voltage (PELV)*. In ad-
dition, pulse and encoder inputs can be isolated from the other terminals on the control card by connecting an
external 24 V DC supply and opening switch 4.
* VLT 5001-5062, 525-600 V do not meet PELV.
Control card, digital/pulse and analog outputs:
No. of programmable digital and analog outputs
2
Terminal nos.
42, 45
Voltage level at digital/pulse output
0 - 24 V DC
Minimum load to ground (terminal 39) at digital/pulse output
600
Frequency ranges (digital output used as pulse output)
0-32 kHz
Current range at analog output
0/4 - 20 mA
Maximum load to ground (terminal 39) at analog output
500
Accuracy of analog output
Max. error: 1.5% of full scale
Resolution on analog output.
8 bit
Reliable galvanic isolation: All digital and analog outputs are galvanically isolated from the supply voltage (PELV)*, as
well as other inputs and outputs.
* VLT 5001-5062, 525-600 V do not meet PELV.
Control card, 24 V DC supply
Terminal nos.
12, 13
Max. load (short-circuit protection)
200 mA
VLT
®
5000 Series
8
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......