Jog is used for overriding the output frequency to the
jog frequency set in parameter 213. The ramp time can
be set in parameter 211. Jog is not active if a stop
command has been given (start-disable). Jog over-
rides stop (operating command, group 2).
Preset reference,
on
is used for shifting between ex-
ternal reference and preset reference. It is assumed
that
External/preset
[2] has been selected in parameter
214. Logic '0' = external references active; logic '1' =
one of the four preset references is active in accord-
ance with the table below.
Preset reference, lsb and Preset reference, msb
enables a choice of one of the four preset references,
in accordance with the table below.
Preset
ref.
msb
Preset ref. lsb
Preset ref. 1
0
0
Preset ref. 2
0
1
Preset ref. 3
1
0
Preset ref. 4
1
1
Freeze reference - freezes the actual reference. The
frozen reference is now the point of enable/condition
for
Speed up
and
Speed down
to be used.
If speed up/down is used, the speed change always
follows ramp 2 (parameters 209/210) in the range 0 -
Ref
MAX
.
Freeze output - freezes the actual motor frequency
(Hz). The frozen motor frequency is now the point of
enable/condition for
Speed up
and
Speed down
to be
used.
If speed up/down is used, the speed change always
follows ramp 2 (parameters 209/210) in the range 0 -
f
M,N
.
NOTE
If
Freeze output
is active, the frequency
converter cannot be stopped via terminals
18 and 19, but only via terminal 27 (to be
programmed for
Coasting stop, inverse
[0]
or
Reset and coasting stop, inverse
[1]).
After
Freeze output
, the PID integrators are reset.
Speed up
and
Speed down are selected if digital con-
trol of the up/down speed is desired (motor potentiom-
eter). This function is only active if
Freeze reference
or
Freeze output
has been selected. As long as there is a
logic `1` on the terminal selected for speed up, the ref-
erence or the output frequency will increase. Follow
ramp 2 (parameter 209) in the range 0 - f
MIN
.
As long as there is a logic `1` on the terminal selected
for speed down, the reference or the output frequency
will be reduced. Follow ramp 2 (parameter 210) in the
range 0 - f
MIN
.
Pulses (logic `1` minimum high for 3 ms and a mini-
mum pause of 3 ms) will lead to a change of speed of
0.1% (reference) or 0.1 Hz (output frequency).
Example:
Terminal
Freeze
ref./
(16)
(17)
Freeze output
No speed change
0
0
1
Speed down
0
1
1
Speed up
1
0
1
Speed down
1
1
1
The speed reference frozen via the control panel can
be changed even if the frequency converter has stop-
ped. The frozen reference will be remembered in case
of a mains drop-out.
Selection of Setup,
lsb and Selection of Setup,
msb
enables a choice of one of the four Setups; how-
ever, this presupposes that parameter 004 has been
set at
Multi Setup
.
Selection of Setup, msb/Speed up and Selection of
Setup, lsb/Speed down
- together with the use of
Freeze reference
or
Freeze output
- enable up/down
speed change.
The selection of Setup occurs in accordance with the
below verification table:
Selection of Setup
Freeze ref/
(32)msb
(33)lsb
Freeze output
Setup 1
0
0
0
Setup 2
0
1
0
Setup 3
1
0
0
Setup 4
1
1
0
No speed change
0
0
1
Speed down
0
1
1
Speed up
1
0
1
Speed down
1
1
1
Catch-up/Slow-down is selected if the reference value
is to be increased or reduced by a programmable per-
centage value set in parameter 219.
Slow-down
Catch-up
Unchanged speed
0
0
Reduced by %-value
1
0
Increased by %-value
0
1
Reduced by %-value
1
1
Ramp 2
is selected if a change between ramp 1 (pa-
rameters 207-208) and ramp 2 (209-210) is desired.
Logic '0' leads to ramp 1, while logic '1' leads to ramp
2.
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
111
Progra
mming
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......