618
Reset of kWh counter
(RESET KWH COUNT)
Value:
No reset (DO NOT RESET)
[0]
Reset (RESET COUNTER)
[1]
Function:
Reset to zero of kWh hour counter (parameter 602).
Description of choice:
If
Reset
[1] has been selected and when the [OK] key
is pressed, the kWh counter of the adjustable frequen-
cy drive is reset. This parameter cannot be selected
via the serial port, RS 485.
NOTE
When the [OK] key has been activated,
the reset has been carried out.
619
Reset of hours-run counter
(RESET RUN. HOUR)
Value:
No reset (DO NOT RESET)
[0]
Reset (RESET COUNTER)
[1]
Function:
Reset to zero of hours-run counter (parameter 601).
Description of choice:
If
Reset
[1] has been selected and when the [OK] key
is pressed, the hours-run counter of the frequency
converter is reset. This parameter cannot be selected
via the serial port, RS 485.
NOTE
When the [OK] key has been activated,
the reset has been carried out.
620
Operating mode
(OPERATION MODE)
Value:
Normal function (NORMAL OPERATION)
[0]
Function with de-activated inverter
(OPER. W/INVERT.DISAB)
[1]
Control card test (CONTROL CARD TEST)
[2]
Initialisation (INITIALIZE)
[3]
Function:
In addition to its normal function, this parameter can
be used for two different tests.
Also, all parameters (except parameters 603-605) can
be initialised.
NOTE
This function will not become active until
the mains supply to the adjustable fre-
quency drive has been turned off and then
turned on again.
Description of choice:
Normal function
[0] is selected for normal operation
with the motor in the selected application.
Function with deactivated inverter
[1] is selected if con-
trol is desired over the influence of the control signal
over the control card and its functions - without the in-
verter driving the motor.
Control card test [2] is selected if control of the analog
and digital inputs, as well as the analog, digital relay
outputs and the +10 V control voltage is desired. A test
connector with internal connections is required for this
test.
Use the following procedure for the control card test:
1.
Select
Control card test
.
2.
Cut off the mains supply and wait for the light
in the display to go out.
3.
Insert the test plug (see below).
4.
Connect to mains.
5.
The adjustable frequency drive expects the
[OK] key to be pressed (if no LCP, set to
Nor-
mal operation
, when the adjustable frequency
drive will start up as usual).
6.
Carry out various tests.
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
151
Progra
mming
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......