Local and remote control
The adjustable frequency drive can be operated man-
ually or remotely. The following is a list of the functions/
commands given via the control panel, the digital in-
puts or the serial communication port in the two situa-
tions (modes).
If parameter 002 is set to Local [1]:
On the LCP, the following keys can be used for local control:
Key:
Parameter:
Data value:
[STOP]
014
[1] Enable
[JOG]
015
[1] Enable
[RESET]
017
[1] Enable
[FWD/REV]
016
[1] Enable
Set parameter 013 for
LCP control and open loop
[1] or
LCP control as parameter 100
[3]:
1. Local reference is set in parameter 003; can be changed via the "+/-" keys.
2. Reversing can be effected by means of the [FWD/REV] key.
Set parameter 013 for
LCP digital control and open loop
[2] or
LCP digital control as parameter 100
[4]:
For the above parameter setting, it is now possible to
control the adjustable frequency drive as follows:
Digital inputs:
1.
Local reference set in parameter 003 can be
changed via the "+/-" keys.
2.
Reset via digital terminal 16, 17, 29, 32 or 33.
3.
Stop inverse via digital terminal 16, 17, 27,
29, 32 or 33.
4.
Choice of Setup, lsb via digital terminal 16,
29 or 32.
5.
Choice of Setup, msb via digital terminal 17,
29 or 33.
6.
Ramp 2 via digital terminal 16, 17, 29, 32 or
33.
7.
Quick-stop via digital terminal 27.
8.
DC braking via digital terminal 27.
9.
Reset and motor coasting stop via digital ter-
minal 27.
10.
Motor coasting stop via digital terminal 27.
11.
Reversing via digital terminal 19.
12.
Choice of Setup, msb/speed up via digital
terminal 32.
13.
Choice of Setup, lsb/speed down via digital
terminal 33.
The serial communication port:
1.
Ramp 2
2.
Reset
3.
Choice of Setup, lsb
4.
Choice of Setup, msb
5.
Relay 01
6.
Relay 04
If parameter 002 is set to Remote control [0]:
Key:
Parameter:
Data value:
[STOP]
014
[1]
[JOG]
015
[1]
[RESET]
017
[1]
VLT
®
5000 Series
188
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......