Special functions
400
Brake function/overvoltage control
(BRAKE FUNCTION)
Value:
Off (OFF)
[0]
Resistor brake (RESISTOR)
[1]
Overvoltage control (OVERVOLTAGE CON-
TROL)
[2]
Overvoltage control and stop
(OVERVOLT CTRL. & STOP)
[3]
Function:
The factory setting is
Off
[0] for VLT 5001-5027
200-240 V, VLT 5001-5102 380-500 V and VLT
5001-5062 525-600 V. For VLT 5032-5052 200-240 V,
5122-5552 380-500 V and VLT 5042-5602 525-690 V
the factory setting is
Overvoltage control
[2].
Resistor brake
[1] is used for programming the adjust-
able frequency drive for connection of a brake resistor.
The connection of a brake resistor allows a higher in-
termediate circuit voltage during braking (generating
operation).
The
Resistor brake
[1] function is only active in units
with an integral dynamic brake (SB and EB units).
Overvoltage control
(excl. brake resistor) can be selec-
ted as an alternative. This function is active for all units
(ST, SB and EB).
The function ensures that a trip can be avoided if the
intermediate circuit voltage increases. This is done by
increasing the output frequency to limit the voltage
from the intermediate circuit. This is a very useful func-
tion, e.g. if the ramp-down time is too short, since
tripping of the adjustable frequency drive is avoided.
In this situation, the ramp-down time is extended.
NOTE
Please note that the ramp-down time is
extended in the case of overvoltage con-
trol, which in some applications may not
be appropriate.
Description of choice:
Select
Resistor brake
[1] if a brake resistor is part of the
system.
Select
Overvoltage control
[2] if the overvoltage control
function is required in all cases - also if stop is pressed.
The adjustable frequency drive will not stop in the case
of a stop command when the overvoltage control is
active.
Select
Overvoltage control and stop
[3] if the overvolt-
age control function is not required during ramp-down
after stop has been pressed.
Warning: If
Overvoltage control
[2] is used
at the same time as the supply voltage to
the adjustable frequency drive is close to
or above the maximum limit, there is a risk
that the motor frequency will increase and
that, consequently, the adjustable fre-
quency drive will not stop the motor when
stop is pressed. If the supply voltage is
higher than:
•
264 V for 200-240 V units
•
550 V for 380-500 V units
•
660 V for 525-600 V units
•
759 V for 525-690 V units
Overvoltage control and stop
[3] should be
selected so that the motor can be stopped.
401
Brake resistor, ohm
(BRAKE RES. (OHM))
Value:
Depends on the unit
Depends on the unit
Function:
This parameter gives the ohmic value of the brake re-
sistor. This value is used for monitoring the power to
the brake resistor provided this function has been se-
lected in parameter 403.
Description of choice:
Set the present resistor value.
402
Braking energy limit, kW
(BR.POWER. LIM.KW)
Value:
Depends on the unit
Depends on the unit
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
125
Progra
mming
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......