Free a data-log if there is a trip and release it when
resetting the adjustable frequency drive. Data-logging
is active when the motor is running.
Digital inputs, parameter 606:
The value for the digital inputs is given as a decimal
figure within the range of 0-255.
The data-log number is stated in square brackets: [1]
175ZA449.10
63.0 %
EXT. REFERENCE, %
606 DATALOG:DIGITALINPUT
[0] 40
Control word, parameter 607:
The value for the control word is given as a decimal
figure within the range of 0-65535.
Status word, parameter 608:
The value for the bus status word is given as a decimal
figure within the range of 0-65535.
Reference, parameter 609:
The value of the reference is stated as a % in the in-
terval 0 - 100%.
Feedback, parameter 610:
The value is stated as the parameterised feedback.
Output frequency, parameter 611:
The value of the motor frequency is stated as a fre-
quency in the interval 0.0 - 999.9 Hz.
Output voltage, parameter 612:
The value of the motor voltage is stated as Volts in the
interval 50 - 1000 V.
Output current, parameter 613:
The value for the motor current is stated as Amps in
the interval 0.0 - 999.9 A.
DC link voltage, parameter 614:
The value of the DC link voltage is stated as Volts in
the interval 0.0 - 999.9 V.
615
Fault log: Error code
(F.LOG: ERROR COD)
Value:
[Index 1 - 10]
Error code 0 - 44
Function:
This parameter makes it possible to see the reason
why a trip occurs.
10 (0-10) log values are stored.
The lowest log number (1) contains the latest/most re-
cently saved data value; the highest log number (10)
contains the oldest data value.
Description of choice:
Given as a number code in which the trip number re-
fers to an alarm code that can be seen in the table in
section
Warnings and Alarms
.
Reset the fault log after manual initialization.
616
Fault log: Time
(F.LOG: TIME)
Value:
[Index 1 - 10]
Function:
This parameter makes it possible to see the total num-
ber of operating hours before the trip occurred. 10
(0-10) log values are stored.
The lowest log number [1] contains the latest/most re-
cently saved data value, while the highest log number
[10] contains the oldest data value.
Description of choice:
Read out as an option.
Indication range: 0.0 - 9999.9.
Reset the fault log after manual initialisation.
617
Fault log: Value
(F.LOG: VALUE)
Value:
[Index 1 - 10]
Function:
This parameter makes it possible to see at what cur-
rent or voltage a given trip occurred.
Description of choice:
Read out as one value.
Indication range: 0.0 - 999.9.
Reset the fault log after manual initialisation.
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
150
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......