Analog input 54 [V] (ANALOG INPUT 54 [V])
[18]
Analog input 60 [mA]
(ANALOG INPUT 60 [mA])
[19]
Pulse reference [Hz] (PULSE REF. [Hz])
[20]
External reference [%] (EXTERNAL REF
[%])
[21]
Status word [Hex] (STATUS WORD [HEX])
[22]
Brake effect/2 min. [KW]
(BRAKE ENERGY/2 min)
[23]
Brake effect/sec. [kW] (BRAKE ENERGY/s)
[24]
Heat sink temp. [°C] (HEATSINK TEMP [°C])
[25]
Alarm word [Hex] (ALARM WORD [HEX])
[26]
Control word [Hex]
(CONTROL WORD [HEX])
[27]
Warning word 1 [Hex]
(WARNING WORD 1 [HEX])
[28]
Warning word 2 [Hex]
(WARNING WORD 2 [HEX])
[29]
Communication option card warning
(Comm opt warn [hex])
[30]
RPM [min
-1
] (MOTOR RPM [RPM])
[31]
RPM x scaling [
-
] (MOTOR RPM x SCALE)
[32]
LCP Display text (FREE PROG. ARRAY)
[33]
Function:
This parameter allows a choice of the data value to be
displayed in line 2 of the display.
Parameters 010-012 enable the use of three additional
data values to be displayed in line 1.
Description of choice:
No readout switches of the readout.
Reference [%]
corresponds to the total reference
(sum of digital/analog/preset/bus/freeze ref./catch-up
and slow-down).
Reference [unit]
gives the status value of terminals
17/29/53/54/60 using the unit stated on the basis of
configuration in parameter 100 (Hz, Hz and rpm).
Feedback [unit]
gives the status value of terminal
33/53/60 using the unit/scale selected in parameter
414, 415 and 416.
Frequency [Hz]
gives the motor frequency, i.e. the
output frequency from the adjustable frequency drive.
Frequency x Scaling [-]
corresponds to the present
motor frequency f
M
(without resonance dampening)
multiplied by a factor (scaling) set in parameter 008.
Motor current [A]
states the phase current of the mo-
tor measured as effective value.
Torque [%]
gives the current motor load in relation to
the rated motor torque.
Power [kW]
states the actual power consumed by the
motor in kW.
Power [HP]
states the actual power consumed by the
motor in HP.
Output energy [kWh]
states the energy consumed by
the motor since the latest reset was made in parameter
618.
Motor voltage [V]
states the voltage supplied to the
motor.
DC link voltage [V]
states the intermediate circuit
voltage in the adjustable frequency drive.
Thermal load, motor [%]
states the calculated/esti-
mated thermal load on the motor. 100% is the cut-out
limit.
Thermal load, VLT [%]
states the calculated/estima-
ted thermal load on the adjustable frequency drive.
100% is the cut-out limit.
Hours run [Hours]
states the number of hours that the
motor has run since the latest reset in parameter 619.
Digital input [Binary code]
states the signal states
from the 8 digital terminals (16, 17, 18, 19, 27, 29, 32
and 33) Input 16 corresponds to the bit at the far left.
'0' = no signal, '1' = connected signal.
Analog input 53 [V]
states the signal value on termi-
nal 53.
Analog input 54 [V]
states the signal value on termi-
nal 54.
Analog input 60 [V]
states the signal value on termi-
nal 60.
Pulse reference [Hz]
states the possible frequency in
Hz connected to the terminals 17 or 29.
External reference [%]
gives the sum of the external
reference as a percentage (the sum of analog/pulse/
bus).
Status word [Hex]
gives the status word sent via the
serial communication port in Hex code from the ad-
justable frequency drive.
Brake power/2 min. [KW]
states the brake power
transferred to an external brake resistor. The mean
power is calculated continuously for the latest 120 sec-
onds.
It is assumed that a resistor value has been entered in
parameter 401.
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
82
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......