Cable lengths, cross-sections and connectors:
Max. motor cable length, screened cable
150 m
Max. motor cable length, unscreened cable
300 m
Max. motor cable length, screened cable VLT 5011 380-500 V
100 m
Max. motor cable length, screened cable VLT 5011 525-600 V and VLT 5008, normal overload mode,
525-600 V
50 m
Max. brake cable length, screened cable
20 m
Max. loadsharing cable length, screened cable
25 m from drive to DC bar.
Max. cable cross-section for motor, brake and loadsharing, see Electrical data
Max. cable cross-section for 24 V external DC supply
- VLT 5001-5027 200-240 V; VLT 5001-5102 380-500 V; VLT 5001-5062 525-600 V
4 mm
2
/10 AWG
- VLT 5032-5052 200-240 V; VLT 5122-5552 380-500 V; VLT 5042-5602 525-690 V
2.5 mm
2
/12 AWG
Max. cross-section for control cables
1.5 mm
2
/16 AWG
Max. cross-section for serial communication
1.5 mm
2
/16 AWG
If UL/cUL is to be complied with, cable with temperature class 60/75°C must be used
(VLT 5001 - 5062 380 - 500 V, 525 - 600 V and VLT 5001 - 5027 200 - 240V).
If UL/cUL is to be complied with, cable with temperature class 75°C must be used
(VLT 5072 - 5552 380 - 500 V, VLT 5032 - 5052 200 - 240 V, VLT 5042 - 5602 525 - 600 V).
Connectors are for use of both copper and aluminium cables, unless other is specified.
Accuracy of display readout (parameters 009-012):
Motor current [6] 0-140% load
Max. error: ±2.0% of rated output current
Torque % [7], -100 - 140% load
Max. error: ±5% of rated motor size
Output [8], power HP [9], 0-90% load
Max. error: ±5% of rated output
Control characteristics:
Frequency range
0 - 1000 Hz
Resolution on output frequency
±0.003 Hz
System response time
3 msec
Speed, control range (open-loop)
1:100 of synchro. speed
Speed, control range (closed-loop)
1:1000 of synchro. speed
Speed, accuracy (open-loop)
< 1500 rpm: max. error ± 7.5 rpm
Speed, accuracy (closed-loop)
< 1500 rpm: max. error ± 1.5 rpm
Torque control accuracy (open-loop)
0-150 rpm: max. error ± 20% of rated torque
Torque control accuracy (speed feedback)
Max. error ± 5% of rated torque
All control characteristics are based on a 4-pole asynchronous motor
Externals:
Enclosure (dependent on power size)
Chassis, Nema1, Nema12
Vibration test
0.7 g RMS 18-1000 Hz random. 3 directions for 2 hours (IEC 68-2-34/35/36)
Max. relative humidity
93 % (IEC 68-2-3) for storage/transport
Max. relative humidity
95 % non condensing (IEC 721-3-3; class 3K3) for operation
Aggresive environment (IEC 721 - 3 - 3)
Uncoated class 3C2
Aggresive environment (IEC 721 - 3 - 3)
Coated class 3C3
Ambient temperature Chassis, NEMA 1(high overload torque 160%)
Max. 45°C (24-hour average max. 40°C)
Ambient temperature Chassis, NEMA 1(normal overload torque 110%)
Max. 40°C (24-hour average max. 35°C)
Ambient temperature NEMA 12 (high overload torque 160%)
Max. 40°C (24-hour average max. 35°C)
VLT
®
5000 Series
10
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......