7.
Press the [OK] key.
8.
Parameter 620 is automatically set to
Normal
operation
.
If a test fails, the adjustable frequency drive will move
into an infinite loop. Replace control card.
Test plugs:
Inialisation
[3] is selected if the factory setting of the unit
is desired without resetting parameters 500, 501 + 600
- 605 + 615 - 617.
NOTE
The motor must be stopped before initial-
isation can be carried out.
Procedure for initializing:
1.
Select Initialisation.
2.
Press the [OK] key.
3.
Cut off the mains supply and wait for the light
in the display to go out.
4.
Connect to mains.
Manual initialisation can be carried out by holding
down three keys at the same time as the mains voltage
is connected. Manual initialisation sets all parameters
to the factory setting, except 600-605. The procedure
for manual initialisation is as follows:
1.
Disconnect the mains voltage and wait for the
light in the display to disappear.
2.
Hold down [DISPLAY/[MENU]+
[OK] while at the same time connecting the
mains supply. The display will now read
MANUAL INITIALIZE.
3.
When the display reads UNIT READY, the
adjustable frequency drive has been initial-
ized.
Parameter no.
Description
Nameplate
Display text
621
VLT type
(VLT TYPE)
622
Power section
(POWER SECTION)
623
VLT ordering number
(VLT ORDERING NO)
624
Software version number
(SOFTWARE VERSION)
625
LCP identification number
(LCP ID NO)
626
Database identification number
(PARAM DB ID)
627
Power section identification number
(POWER UNIT DB ID)
628
Application option type
(APP. OPTION)
629
Application option ordering number
(APP. ORDER NO)
630
Communication option type
(COM. OPTION)
631
Communication option ordering number
(COM. ORDER NO)
Function:
The key data of the unit can be read out via the display
or the serial communication port.
Description of choice:
VLT type
, parameter 621:
VLT Type indicates the unit size and basic function
concerned.
For example: VLT 5008 380-500 V.
Power section, parameter 622:
The power section states the given power section be-
ing used.
For example: Extended with brake.
VLT
®
5000 Series
152
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......