5032-5052 200-240 V, VLT 5122-5552 380-500 V and
5042-5602 525-690 V the factory setting is 66 Hz.
See also parameter 205.
NOTE
The output frequency of the adjustable
frequency drive can never assume a value
higher than 1/10 of the switching frequen-
cy.
Description of choice:
A value from f
MIN
to the choice made in parameter 200
can be selected.
NOTE
If the maximum motor frequency is set at
more than 500 Hz, parameter 446 must be
set at
60° AVM
[0] switching pattern.
203
Reference/feedback area
(REF/FEEDB. RANGE)
Value:
Min - Max (MIN - MAX)
[0]
- Max - + Max (-MAX-+MAX)
[1]
Function:
This parameter decides whether the reference signal
and the feedback signal are to be positive or can be
both positive and negative.
The minimum limit may be a negative value, unless
Speed control, closed loop
has been selected
(parameter 100).
Choose
Min - Max
[0] if
Process control, closed loop
has been selected in parameter 100.
Description of choice:
Choose the desired range.
204
Minimum reference
(MIN. REFERENCE)
Value:
-100,000.000 - Ref
MAX
0.000
Depends on parameter 100.
Function:
The
Minimum reference
gives the minimum value that
can be assumed by the sum of all references.
Minimum
reference
is only active if
Min - Max
[0] has been set
in parameter 203; however, it is always active in
Proc-
ess control, closed loop
(parameter 100).
Description of choice:
Is only active when parameter 203 has been set to
Min
- Max
[0].
Set the desired value.
The unit follows the choice of configuration in param-
eter 100.
Speed control, open loop:
Hz
Speed control, closed loop:
rpm
Torque control, open loop:
Nm
Torque control, speed feedback:
Nm
Process control, closed loop:
Process units
(par.
416)
Special motor characteristics, activated in parameter
101, use the unit selected in parameter 100.
205
Maximum reference
(MAX. REFERENCE)
Value:
Ref
MIN
- 100,000.000
50.000
Function:
The
Maximum reference
gives the highest value that
can be assumed by the sum of all references. If closed
loop has been selected in parameter 100, the maxi-
mum reference cannot be set higher than the maxi-
mum feedback (parameter 415).
Description of choice:
Set the desired value.
The unit follows the choice of configuration in param-
eter 100.
Speed control, open loop:
Hz
Speed control, closed loop:
rpm
Torque control, open loop:
Nm
Torque control, speed feedback:
Nm
Process control, closed loop:
Process units
(par.
416)
Special motor characteristics, activated in parameter
101, use the unit selected in parameter 100.
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
101
Progra
mming
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......