Compact, AC line supply 3 x 380-500 V
According to international requirements
VLT type
5062
5072
5102
Normal overload torque (110 %):
Output current
I
VLT,N
[A] (380-440 V)
106
147
177
I
VLT, MAX
(60 s) [A] (380-440 V)
117
162
195
I
VLT,N
[A] (441-500 V)
106
130
160
I
VLT, MAX
(60 s) [A] (441-500 V)
117
143
176
Output
S
VLT,N
[kVA] (380-440 V)
80.8
102
123
S
VLT,N
[kVA] (441-500 V)
91.8
113
139
Typical shaft output
P
VLT,N
[kW] (400 V) 55
75
90
P
VLT,N
[HP] (460 V) 75
100
125
P
VLT,N
[kW] (500 V)
75
90
110
High overload torque (160 %):
Output current
I
VLT,N
[A] (380-440 V)
90
106
147
I
VLT, MAX
(60 s) [A] (380-440 V)
135
159
221
I
VLT,N
[A] (441-500 V)
80
106
130
I
VLT, MAX
(60 s) [A] (441-500 V)
120
159
195
Output
S
VLT,N
[kVA] (380-440 V)
68.6
73.0
102
S
VLT,N
[kVA] (441-500 V)
69.3
92.0
113
Typical shaft output
P
VLT,N
[kW] (400 V) 45
55
75
P
VLT,N
[HP] (460 V) 60
75
100
P
VLT,N
[kW] (500 V)
55
75
90
Max. cable cross-section to motor,
IP 54
50/0
5)
150/300
mcm
6)
150/300
mcm
6)
brake and load sharing [mm
2
]/[AWG]
2)
IP 20
50/0
5)
120/250
mcm
5)
120/250
mcm
5)
Min. cable cross-section to motor,
brake and load sharing [mm
2
]/[AWG]
4)
16/6
25/4
25/4
Rated input current
I
L,N
[A] (380 V)
104
145
174
I
L,N
[A] (460 V)
104
128
158
Max. cable cross-section
IP 54
50/0
5)
150/300
mcm
150/300
mcm
power[mm
2
]/[AWG]
2)
IP 20
50/0
5)
120/250
mcm
5)
120/250
mcm
5)
Max. pre-fuses
[-]/UL
1)
[A]
160/150 225/225 250/250
Efficiency
3)
>0.97
>0.97
>0.97
Weight IP 20 EB
[kg]
43
54
54
Weight IP 54
[kg]
60
77
77
Power loss at max. load.
- high overload torque (160 %)
[W]
1122
1058
1467
- normal overload torque (110 %)
[W]
1322
1467
1766
Enclosure
IP20/
IP 54
IP20/
IP 54
IP20/
IP 54
1. For type of fuse, see section
Fuses.
2. American Wire Gauge.
3. Measured using 100 ft [30 m] shielded motor cables at rated load and rated frequency.
4. Min. cable cross-section is the smallest cable cross-section allowed to be fitted on the terminals to comply with IP 20. Always comply
with national and local regulations on min. cable cross-section.
5. Aluminum cables with cross-section above 0.054 in
2
[35 mm
2
] must be connected by use of an AI-Cu connector.
used.
6. Brake and load sharing: 95 mm
2
/ AWG 3/0
VLT
®
5000 Series
20
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......