Fuses
UL compliance
To comply with UL/cUL approvals, pre-fuses according to the table below must be used.
200-240 V
VLT
Bussmann
SIBA
Littel fuse
Ferraz-Shawmut
5001
KTN-R10
5017906-010
KLN-R10
ATM-R10 or A2K-10R
5002
KTN-R10
5017906-010
KLN-R10
ATM-R10 or A2K-10R
5003
KTN-R25
5017906-016
KLN-R15
ATM-R15 or A2K-15R
5004
KTN-R20
5017906-020
KLN-R20
ATM-R20 or A2K-20R
5005
KTN-R25
5017906-025
KLN-R25
ATM-R25 or A2K-25R
5006
KTN-R30
5012406-032
KLN-R30
ATM-R30 or A2K-30R
5008
KTN-R50
5014006-050
KLN-R50
A2K-50R
5011
KTN-R60
5014006-063
KLN-R60
A2K-60R
5016
KTN-R85
5014006-080
KLN-R80
A2K-80R
5022
KTN-R125
2028220-125
KLN-R125
A2K-125R
5027
KTN-R125
2028220-125
KLN-R125
A2K-125R
5032
KTN-R150
2028220-160
L25S-150
A25X-150
5042
KTN-R200
2028220-200
L25S-200
A25X-200
5052
KTN-R250
2028220-250
L25S-250
A25X-250
380-500 V
Bussmann
SIBA
Littel fuse
Ferraz-Shawmut
5001
KTS-R6
5017906-006
KLS-R6
ATM-R6 or A6K-6R
5002
KTS-R6
5017906-006
KLS-R6
ATM-R6 or A6K-6R
5003
KTS-R10
5017906-010
KLS-R10
ATM-R10 or A6K-10R
5004
KTS-R10
5017906-010
KLS-R10
ATM-R10 or A6K-10R
5005
KTS-R15
5017906-016
KLS-R16
ATM-R16 or A6K-16R
5006
KTS-R20
5017906-020
KLS-R20
ATM-R20 or A6K-20R
5008
KTS-R25
5017906-025
KLS-R25
ATM-R25 or A6K-25R
5011
KTS-R30
5012406-032
KLS-R30
A6K-30R
5016
KTS-R40
5012406-040
KLS-R40
A6K-40R
5022
KTS-R50
5014006-050
KLS-R50
A6K-50R
5027
KTS-R60
5014006-063
KLS-R60
A6K-60R
5032
KTS-R80
2028220-100
KLS-R80
A6K-180R
5042
KTS-R100
2028220-125
KLS-R100
A6K-100R
5052
KTS-R125
2028220-125
KLS-R125
A6K-125R
5062
KTS-R150
2028220-160
KLS-R150
A6K-150R
5072
FWH-220
2028220-200
L50S-225
A50-P225
5102
FWH-250
2028220-250
L50S-250
A50-P250
5122*
FWH-300/170M3017
2028220-315
L50S-300
A50-P300
5152*
FWH-350/170M3018
2028220-315
L50S-350
A50-P350
5202*
FWH-400/170M4012
206xx32-400
L50S-400
A50-P400
5252*
FWH-500/170M4014
206xx32-500
L50S-500
A50-P500
5302*
FWH-600/170M4016
206xx32-600
L50S-600
A50-P600
5352
170M4017
2061032,700
6.9URD31D08A0700
5452
170M6013
2063032,900
6.9URD33D08A0900
5502
170M6013
2063032,900
6.9URD33D08A0900
5552
170M6013
2063032,900
6.9URD33D08A0900
* Circuit Breakers manufactured by General Electric, Cat. No. SKHA36AT0800, with rating plugs listed below can be used to meet UL-
requirements:
5122
rating plug No.
SRPK800 A 300
5152
rating plug No.
SRPK800 A 400
5202
rating plug No.
SRPK800 A 400
5252
rating plug No.
SRPK800 A 500
5302
rating plug No.
SRPK800 A 600
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
33
Technical data
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......