525-600 V
Bussmann
SIBA
Littel fuse
Ferraz-Shawmut
5001
KTS-R3
5017906-004
KLS-R003
A6K-3R
5002
KTS-R4
5017906-004
KLS-R004
A6K-4R
5003
KT-R5
5017906-005
KLS-R005
A6K-5R
5004
KTS-R6
5017906-006
KLS-R006
A6K-6R
5005
KTS-R8
5017906-008
KLS-R008
A6K-8R
5006
KTS-R10
5017906-010
KLS-R010
A6K-10R
5008
KTS-R15
5017906-016
KLS-R015
A6K-15R
5011
KTS-R20
5017906-020
KLS-R020
A6K-20R
5016
KTS-R30
5017906-030
KLS-R030
A6K-30R
5022
KTS-R35
5014006-040
KLS-R035
A6K-35R
5027
KTS-R45
5014006-050
KLS-R045
A6K-45R
5032
KTS-R60
5014006-063
KLS-R060
A6K-60R
5042
KTS-R75
5014006-080
KLS-R075
A6K-80R
5052
KTS-R90
5014006-100
KLS-R090
A6K-90R
5062
KTS-R100
5014006-100
KLS-R100
A6K-100R
525-600 V (UL) and 525-690 V (CE) drives
Bussmann
SIBA
FERRAZ-SHAWMUT
5042
170M3013
2061032,125
6.6URD30D08A0125
5052
170M3014
2061032,16
6.6URD30D08A0160
5062
170M3015
2061032,2
6.6URD30D08A0200
5072
170M3015
2061032,2
6.6URD30D08A0200
5102
170M3016
2061032,25
6.6URD30D08A0250
5122
170M3017
2061032,315
6.6URD30D08A0315
5152
170M3018
2061032,35
6.6URD30D08A0350
5202
170M4011
2061032,35
6.6URD30D08A0350
5252
170M4012
2061032,4
6.6URD30D08A0400
5302
170M4014
2061032,5
6.6URD30D08A0500
5352
170M5011
2062032,55
6.6URD32D08A550
5402
170M4017
2061032,700
6.9URD31D08A0700
5502
170M6013
2063032,900
6.9URD33D08A0900
5602
170M6013
2063032,900
6.9URD33D08A0900
KTS-fuses from Bussmann may substitute KTN for 240 V drives.
FWH-fuses from Bussmann may substitute FWX for 240 V drives.
KLSR fuses from LITTEL FUSE may substitute KLNR fuses for 240 V drives.
L50S fuses from LITTEL FUSE may substitute L25S fuses for 240 V drives.
A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240 V drives.
A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240 V drives.
Non UL compliance
If UL/cUL is not to be complied with, we recommend the above mentioned fuses or:
VLT 5001-5027
200-240 V
type gG
VLT 5032-5052
200-240 V
type gR
VLT 5001-5062
380-500 V
type gG
VLT 5072-5102
380-500 V
type gR
VLT 5122-5302
380-500 V
type gG
VLT 5352-5552
380-500 V
type gR
VLT 5001-5062
525-600 V
type gG
Not following the recommendation may result in unnecessary damage of the drive in case of malfunction. Fuses must be designed for
protection in a circuit capable of supplying a maximum of 100000 A
rms
(symmetrical), 500/600 V maximum.
VLT
®
5000 Series
34
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......