PN
U
Parameter
Factory setting
Range
Chang
es
4-Setup
Conversion Data
#
description
during operation
index
type
300 Terminal 16, input
Reset
Yes
Yes
0
5
301 Terminal 17, input
Freeze reference
Yes
Yes
0
5
302 Terminal 18 Start, input
Start
Yes
Yes
0
5
303 Terminal 19, input
Reversing
Yes
Yes
0
5
304 Terminal 27, input
Coasting stop, inverse
Yes
Yes
0
5
305 Terminal 29, input
Jog
Yes
Yes
0
5
306 Terminal 32, input
Choice of setup, msb/speed up
Yes
Yes
0
5
307 Terminal 33, input
Choice of setup, lsb/speed down
Yes
Yes
0
5
308 Terminal 53, analogue input voltage Reference
Yes
Yes
0
5
309 Terminal 53, min. scaling
0.0 V
0.0 - 10.0 V
Yes
Yes
-1
5
310 Terminal 53, max. scaling
10.0 V
0.0 - 10.0 V
Yes
Yes
-1
5
311 Terminal 54, analogue input voltage No operation
Yes
Yes
0
5
312 Terminal 54, min. scaling
0.0 V
0.0 - 10.0 V
Yes
Yes
-1
5
313 Terminal 54, max. scaling
10.0 V
0.0 - 10.0 V
Yes
Yes
-1
5
314 Terminal 60, analogue input current
Reference
Yes
Yes
0
5
315 Terminal 60, min. scaling
0.0 mA
0.0 - 20.0 mA
Yes
Yes
-4
5
316 Terminal 60, max. scaling
20.0 mA
0.0 - 20.0 mA
Yes
Yes
-4
5
317 Time out
10 sec.
1 - 99 sec.
Yes
Yes
0
5
318 Function after time out
Off
Yes
Yes
0
5
319 Terminal 42, output
0 - I
MAX
Þ 0-20 mA
Yes
Yes
0
5
320 Terminal 42, output, pulse scaling
5000 Hz
1 - 32000 Hz
Yes
Yes
0
6
321 Terminal 45, output
0 - f
MAX
Þ 0-20 mA
Yes
Yes
0
5
322 Terminal 45, output, pulse scaling
5000 Hz
1 - 32000 Hz
Yes
Yes
0
6
323 Relay 01, output
Ready - no thermal warning
Yes
Yes
0
5
324 Relay 01, ON delay
0.00 sec.
0.00 - 600 sec.
Yes
Yes
-2
6
325 Relay 01, OFF delay
0.00 sec.
0.00 - 600 sec.
Yes
Yes
-2
6
326 Relay 04, output
Ready - remote control
Yes
Yes
0
5
327 Pulse reference, max. frequency
5000 Hz
Yes
Yes
0
6
328 Pulse feedback, max. frequency
25000 Hz
Yes
Yes
0
6
329 Encoder feedback pulse/rev.
1024 pulses/rev.
1 - 4096 pulses/
rev.
Yes
Yes
0
6
330 Freeze reference/output function
No operation
Yes
No
0
5
345 Encoder loss timeout
1 sec.
0 - 60 sec
Yes
Yes
-1
6
346 Encoder loss function
OFF
Yes
Yes
0
5
357 Terminal 42, Output minimum scaling 0 %
000 - 100%
Yes
Yes
0
6
358 Terminal 42, Output maximum scal-
ing
100%
000 - 500%
Yes
Yes
0
6
359 Terminal 45, Output minimum scaling 0 %
000 - 100%
Yes
Yes
0
6
360 Terminal 45, Output maximum scal-
ing
100%
000 - 500%
Yes
Yes
0
6
361 Encoder loss threshold
300%
000 - 600 %
Yes
Yes
0
6
VLT
®
5000 Series
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
223
Parameters
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......