Function:
This parameter sets the Y-value of the 3rd break point.
Description of choice:
Set the voltage desired at the F3 frequency set in pa-
rameter 428.
See drawing for parameter 422.
428
F 3 frequency
(F3 FREQUENCY)
Value:
par. 426 - par. 430
Factory setting of par. 104
Function:
This parameter sets the X-value of the 3rd break point.
Description of choice:
Set the frequency desired at the U3 voltage set in pa-
rameter 427.
See drawing for parameter 422.
429
U 4 voltage
(U4 VOLTAGE)
Value:
0.0 - U
VLT,MAX
Factory setting of par. 103
Function:
This parameter sets the Y-value of the 4th break point.
Description of choice:
Set the voltage desired at the F4 frequency set in pa-
rameter 430.
See drawing for parameter 422.
430
F 4 frequency
(F4 FREQUENCY)
Value:
par. 428 - par. 432
Factory setting of par. 104
Function:
This parameter sets the X-value of the 4th break point
Description of choice:
Set the frequency desired at the U4 voltage set in pa-
rameter 429.
See drawing for parameter 422.
431
U 5 voltage
(U5 VOLTAGE)
Value:
0.0 - U
VLT, MAX
Factory setting of par. 103
Function:
This parameter sets the Y-value of the 5th break point.
Description of choice:
Set the voltage desired at the F5 frequency set in pa-
rameter 432.
432
F 5 frequency
(F5 FREQUENCY)
Value:
par. 430 - 1000 Hz
Factory setting of par. 104
Function:
This parameter sets the X-value of the 5th break point.
This parameter is not limited by parameter 200.
Description of choice:
Set the frequency desired at the U5 voltage set in pa-
rameter 431.
See drawing for parameter 422.
433
Torque control, open loop proportional
gain
(TOR-OL PROP. GAIN)
Value:
0 (Off) - 500%
100%
Function:
The proportional gain indicates how many times the
error (the deviation between feedback signal and set
point) is to be applied.
Used together with
Torque control, open loop
(param-
eter 100).
Description of choice:
Fast control is obtained with a high gain, but if the gain
is too high, the process may become unstable.
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
134
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...