37 kW (37.00 KW)
[3700]
45 kW (45.00 KW)
[4500]
55 kW (55.00 KW)
[5500]
75 kW (75.00 KW)
[7500]
90 kW (90.00 KW)
[9000]
110 kW (110.00 KW)
[11000]
132 kW (132.00 KW)
[13200]
160 kW (160.00 KW)
[16000]
200 kW (200.00 KW)
[20000]
250 kW (250.00 KW)
[25000]
280 kW (280.00 KW)
[28000]
315 kW (315.00 KW)
[31500]
355 kW (355.00 KW)
[35500]
400 kW (400.00 KW)
[40000]
450 kW (450.00 KW)
[45000]
500 kW (500.00 KW)
[50000]
530 kW (530.00 KW)
[53000]
560 kW (560.00 KW)
[56000]
630 kW (630.00 KW)
[63000]
Depends on the unit
Function:
Selects the kW value that corresponds to the rated
power of the motor.
A rated kW value has been selected from the factory
that depends on the unit size.
Description of choice:
Select a value that equals the nameplate data on the
motor. There are 4 possible undersizes or 1 oversize
in comparison with the factory setting.
Also, alternatively it is possible to set the value for mo-
tor power as an infinitely variable value.
The set value automatically changes the values of the
motor parameters in parameter 108-118.
NOTE
If the setting in parameter 102-109 is
changed, parameter 110-118 will return to
factory setting. If using special motor char-
acteristics a change in parameter 102-109
affects parameter 422.
103
Motor voltage (MOTOR VOLTAGE)
Value:
200 V
[200]
208 V
[208]
220 V
[220]
230 V
[230]
240 V
[240]
380 V
[380]
400 V
[400]
415 V
[415]
440 V
[440]
460 V
[460]
480 V
[480]
500 V
[500]
550 V
[550]
575 V
[575]
660 V
[660]
690 V
[690]
Depends on the unit.
Function:
Select a value that equals the nameplate data on the
motor.
NOTE
The motor will always see the peak volt-
age, corresponding to the connected sup-
ply voltage. In case of regenerative oper-
ation, the voltage can be higher.
Description of choice:
Select a value that equals the nameplate data on the
motor, regardless of the AC line voltage of the adjust-
able frequency drive. Furthermore, it is also possible
to set the value of the motor voltage at an infinitely
variable rate.
The value set automatically changes values for the
motor parameters in parameters 108-118.
For 87 Hz operation with 230/400 V motors, set the
nameplate data for 230 V. Adapt parameter 202
Out-
put frequency high limit
and parameter 205
Maximum
reference
to the 87 Hz application.
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
89
Progra
mming
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......