7.
If the intermediate circuit voltage is higher
than the intermediate circuit voltage -2% be-
fore the brake test, discontinue the brake
check and give off a warning or alarm.
8.
Brake check OK.
Description of choice:
If
Off
[0] is selected, this function will still monitor
whether the brake resistor and the brake IGBT short-
circuit during operation, in which case it will give off a
warning. If
Warning
[1] is selected, the brake resistor
and brake IGBT will be monitored with respect to short-
circuiting. In addition, on power-up it will be checked
whether the brake resistor has been disconnected.
NOTE
A warning in connection with
Off
[0] or
Warning
[1] can only be removed by dis-
connecting the mains supply and turning
it back on, provided the fault has been
corrected. Please note that in connection
with
Off
[0] or
Warning
[1] the adjustable
frequency drive will continue even if a fault
has been found.
In the case of
Trip
[2], the adjustable frequency drive
will cut out while giving an alarm (trip locked) if the
brake resistor has short-circuited or been disconnec-
ted or if the brake IGBT has short-circuited.
405
Reset function (RESET MODE)
Value:
Manual reset (MANUAL RESET)
[0]
Automatic reset x 1 (AUTOMATIC X 1)
[1]
Automatic reset x 2 (AUTOMATIC X 2)
[2]
Automatic reset x 3 (AUTOMATIC X 3)
[3]
Automatic reset x 4 (AUTOMATIC X 4)
[4]
Automatic reset x 5 (AUTOMATIC X 5)
[5]
Automatic reset x 6 (AUTOMATIC X 6)
[6]
Automatic reset x 7 (AUTOMATIC X 7)
[7]
Automatic reset x 8 (AUTOMATIC X 8)
[8]
Automatic reset x 9 (AUTOMATIC X 9)
[9]
Automatic reset x 10 (AUTOMATIC X 10)
[10]
Function:
This parameter makes it possible to select the reset
function desired after tripping.
After reset, the adjustable frequency drive can be re-
started.
Description of choice:
If
Manual reset
[0] is selected, reset must be effected
via the [RESET] key or via the digital inputs.
If the adjustable frequency drive is to carry out an au-
tomatic reset (1-10 times) after tripping, select data
value [1]-[10].
NOTE
The internal AUTOMATIC RESET coun-
ter is reset 10 minutes after the first AU-
TOMATIC RESET has occurred.
Warning: The motor may start without
warning.
406
Automatic restart time
(AUT RESTART TIME)
Value:
0 - 10 sec.
5 sec.
Function:
This parameter allows setting of the time from tripping
until the automatic reset function begins.
It is assumed that automatic reset has been selected
in parameter 405.
Description of choice:
Set the desired time.
407
Mains failure
(MAINS FAILURE)
Value:
No function (NO FUNCTION)
[0]
Controlled ramp-down
(CONTROL RAMP DOWN)
[1]
Controlled ramp-down and trip
(CTRL. RAMP DOWN-TRIP)
[2]
VLT
®
5000 Series
= factory setting, () = display text, [] = value for use in communication via serial communication port
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
127
Progra
mming
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......