Compact, AC line supply 3 x 380-500 V
According to international requirements
VLT type 5352
5452
5502
5552
Normal overload current (110%):
Output current
I
VLT,N
[A] (380-440 V) 600
658
745
800
I
VLT, MAX
(60 s) [A] (380-440
V)
660
724
820
880
I
VLT,N
[A] (441-500 V) 540
590
678
730
I
VLT, MAX
(60 s) [A] (441-500
V)
594
649
746
803
Output
S
VLT,N
[kVA] (400 V) 416
456
516
554
S
VLT,N
[kVA] (460 V) 430
470
540
582
S
VLT,N
[kVA] (500 V) 468
511
587
632
Typical shaft output
[kW] (400 V) 315
355
400
450
[HP] (460 V) 450
500
550/600
600
[kW] (500 V) 355
400
500
530
High overload torque (160 %):
Output current
I
VLT,N
[A] (380-440 V) 480
600
658
695
I
VLT, MAX
(60 s) [A] (380-440
V)
720
900
987
1042
I
VLT,N
[A] (441-500 V) 443
540
590
678
I
VLT, MAX
(60 s) [A] (441-500
V)
665
810
885
1017
Output
S
VLT,N
[kVA] (400 V) 333
416
456
482
S
VLT,N
[kVA] (460 V) 353
430
470
540
S
VLT,N
[kVA] (500 V) 384
468
511
587
Typical shaft output
[kW] (400 V) 250
315
355
400
[HP] (460 V) 350
450
500
550
[kW] (500 V) 315
355
400
500
Max. cable cross-section
to motor and load sharing
[mm
2
]
4,6
[AWG]
2,4,6
4x240
4x500 mcm
Max. cable cross-section
to brake
[mm
2
]
4,6
[AWG]
2,4,6
2x185
2x350 mcm
Normal overload current (110%):
Rated input current
I
L,N
[A] (380-440 V) 590
647
733
787
I
L,N
[A] (441-500 V) 531
580
667
718
High overload torque (160 %):
Rated input current
I
L,N
[A] (380-440 V) 472
590
647
684
I
L,N
[A] (441-500 V) 436
531
580
667
Max. cable cross-section
power supply
[mm
2
]
4,6
[AWG]
2,4,6
4x240
4x500 mcm
Max. pre-fuses (line) [-]/
UL
[A]
1
700/700
900/900
900/900
900/900
Efficiency
3
0,98
Power loss
Normal overload [W] 7630
7701
8879
9428
High overload [W] 6005
6960
7691
7964
Weight
IP 00 [kg] 221
234
236
277
Weight
IP 21/NEMA 1 [kg] 263
270
272
313
Weight
IP 54/NEMA 12 [kg] 263
270
272
313
Enclosure
IP 00, IP 21/NEMA 1 and IP 54/NEMA 12
1. For type of fuse, see section
Fuses.
2. American Wire Gauge.
3. Measured using 100 ft [30 m] shielded motor cables at rated load and rated frequency.
4. Max. cable cross-section is the maximum possible cable cross-section allowed to be fitted on the terminals. Always comply with
national and local regulations on min. cable cross-section.
5. Weight without shipping container.
6. Connection bolt power supply, motor and load sharing: M10 (compression lug), 2xM8 (box lug), M8 (brake)
VLT
®
5000 Series
22
MG.51.C5.22 - VLT
p
is a registered Danfoss trademark.
Summary of Contents for VLT 5000 Series
Page 2: ...VLT 5000 Instruction Manual ...
Page 3: ......
Page 185: ...VLT 5000 Series 182 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 186: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 183 EC EMC ...
Page 197: ...EXTERNAL PRESET VLT 5000 Series 194 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 202: ...VLT 5000 Series MG 51 C5 22 VLT p is a registered Danfoss trademark 199 List of functions ...
Page 217: ...VLT 5000 Series 214 MG 51 C5 22 VLT p is a registered Danfoss trademark ...
Page 239: ......