Chapter 6 - Parameter Description [APP]
6-68
count time for Auto Change is depend on Auto Change
Mode (APP-26). In mode ‘0’, inverter starts counting only
when auxiliary motor is running. In mode ‘1’ or ‘2’, inverter
starts counting when any motor is running including main
motor.
APP-29: Inter-Lock Selection
By setting this code to ‘Yes’, the multi-function input
terminals (P1 ~ P4) are used as auxiliary motor operating
condition of RLY1, RLY2, RLY3, and AUX. The multi-
function input terminal should be turned on to run the
corresponding auxiliary motor. If running with any multi-
function input terminal open with this function, the inverter
starts motors except the corresponding motor. If multi-
function input happens to be turned off during motor
running, the inverter stops all running motors and restarts
running with only normal motors except the subject motor.
By setting this parameter to ‘Yes’, the multi-function input
terminals (P1~P4) are set to ‘Interlock1’ through
‘Interlock4’ automatically.
☞
Note:
P1 through P4 cannot be used for other purpose it
this code is set to ‘Yes’.
APP-30: Actual Value Display
This code displays the value using on PID controller in
frequency.
APP-31: Actual Value Display in Percentage
This code displays the value using on PID controller in
percentage.
APP-32: Draw Mode Selection
This code sets the signal input to use for Draw operation.
The main reference frequency is set in DRV-04. This
parameter should be set to a signal that is not selected in
DRV-04.
APP-33: Draw Size Setting
This code sets the frequency bandwidth during Draw
operation. For example, when Reference Frequency
(DRV-00) is set to ‘30Hz’, Draw Mode (APP-32) to
‘V1_Draw’ and Draw Size (APP-33) to ‘10%’, the
frequency difference during Draw operation is between 27
Hz and 33Hz. The following figure shows the block
diagram for Draw and Override operation.
APP
►
Inter-lock
29 --- No ---
0
29
Factory Default:
No
0
Related Functions:
I/O-12 to I/O-14 [Multi-Function Input]
EXT-02 to EXT-04 [Multi-Function Input]
APP
►
Actual Value
30 0.00 Hz
0.00
30
Factory Default:
0.00
Hz
0.00
APP
►
Actual Perc
31 0 %
0
31
Factory Default:
0
%
0
APP
►
Draw Mode
32 None
0
32
Factory Default:
None
0
APP
►
Draw Perc
33 100 %
100
33
Factory Default:
100%
100
Summary of Contents for 30 HP30
Page 6: ......
Page 12: ......
Page 16: ...Chapter 1 Installation 1 4 BLANK ...
Page 18: ...Chapter 1 Installation 1 6 BLANK ...
Page 28: ...Chapter 1 Installation 1 16 Notes ...
Page 39: ...Chapter 2 Operation 2 11 Notes ...
Page 40: ......
Page 46: ......
Page 60: ...Chapter 4 Operation Examples 4 14 Notes ...
Page 83: ...Chapter 5 Parameter List 5 23 Notes ...
Page 84: ......
Page 92: ...Chapter 6 Parameter Description DRV 6 8 Notes ...
Page 105: ......
Page 106: ...Chapter 6 Parameter description FU1 6 14 Notes ...
Page 126: ...Chapter 6 Parameter Description FU2 6 34 Notes ...
Page 144: ...Chapter 6 Parameter Description I O 6 52 Notes ...
Page 162: ......
Page 188: ...Chapter 7 Options 7 26 Type 1 Max 400 Watt Type 2 Max 600 Watt A ...
Page 189: ...Chapter 7 Options 7 27 Type 3 ...
Page 194: ......
Page 204: ......
Page 210: ......