Chapter 6 - Parameter Description [FU2]
6-30
FU2-69: Accel/Decel Change Frequency
This function is used to change Accel/Decel ramp at a
certain frequency. This is useful in textile machine
application.
☞
Note:
If the multi-function input terminal (I/O-12 ~ I/O-14) is
set to ‘XCEL-L’, XCEL-M’, or XCEL-H’, The Multi-
Accel/Decel Time (I/O-25 ~ I/O-38) has the priority.
[Accel/Decel Change Operation]
FU2-70: Reference Frequency for Accel/Decel
This is the reference frequency for acceleration and
deceleration. If a decided Accel/Decel time from a
frequency to a target frequency is required, set this value
to ‘Delta freq’.
Setting Range
LCD 7-Seg
Description
Max freq
0
The Accel/Decel time is the time that
takes to reach the maximum
frequency from 0 Hz.
Delta freq
1
The Accel/Decel time is the time that
takes to reach a target frequency
from a frequency (currently operating
frequency).
FU2-71: Accel/Decel Time Scale
This is used to change the time scale.
Setting Range
LCD 7-Seg
Description
0.01 sec
0
The Accel/Decel time is changed by 0.01
second. The maximum setting range is
600 seconds.
0.1 sec
1
The Accel/Decel time is changed by 0.1
second. The maximum setting range is
6000 seconds.
1 sec
2
The Accel/Decel time is changed by 1
second. The maximum setting range is
60000 seconds.
FU2-72: Power On Display
This code selects the parameter to be displayed first on
keypad (DRV-00) when the power is turned on.
Setting
Range
Description
0
DRV-00 [Command Frequency]
1
DRV-01 [Acceleration Time]
2
DRV-02 [Deceleration Time]
3
DRV-03 [Drive Mode]
FU2
►
Acc/Dec freq
70 Max freq
0
70
Factory Default:
Max freq
0
Related Functions:
DRV-01, DRV-02 [Accel/Decel Time]
FU2-71 [Accel/Decel Time Scale]
I/O-25 ~ I/O-38 [1
st
~ 7
th
Accel/Decel Time]
FU2
►
Time scale
71 0.1 sec
0.1
71
Factory Default:
0.1 sec
0.1
Related Functions:
DRV-01, DRV-02 [Accel/Decel Time]
FU2-70 [Reference Freq. for Accel/Decel]
I/O-25 ~ I/O-38 [1
st
~ 7
th
Accel/Decel Time]
FU2
►
Acc/Dec ch F
69 0.00 Hz
0
69
Factory Default:
0.00 Hz
0
Output Frequency
FX
Max. Frequency
Accel/Decel
Change
Frequency
DRV-01 [AccTime]
DRV-02 [DecTime]
I/O-25 [Acc Time1]
I/O-26 [Dec Time1]
FU2
►
PowerOn disp
72 0
0
72
Factory Default:
0
0
Summary of Contents for 30 HP30
Page 6: ......
Page 12: ......
Page 16: ...Chapter 1 Installation 1 4 BLANK ...
Page 18: ...Chapter 1 Installation 1 6 BLANK ...
Page 28: ...Chapter 1 Installation 1 16 Notes ...
Page 39: ...Chapter 2 Operation 2 11 Notes ...
Page 40: ......
Page 46: ......
Page 60: ...Chapter 4 Operation Examples 4 14 Notes ...
Page 83: ...Chapter 5 Parameter List 5 23 Notes ...
Page 84: ......
Page 92: ...Chapter 6 Parameter Description DRV 6 8 Notes ...
Page 105: ......
Page 106: ...Chapter 6 Parameter description FU1 6 14 Notes ...
Page 126: ...Chapter 6 Parameter Description FU2 6 34 Notes ...
Page 144: ...Chapter 6 Parameter Description I O 6 52 Notes ...
Page 162: ......
Page 188: ...Chapter 7 Options 7 26 Type 1 Max 400 Watt Type 2 Max 600 Watt A ...
Page 189: ...Chapter 7 Options 7 27 Type 3 ...
Page 194: ......
Page 204: ......
Page 210: ......