Chapter 6 - Parameter Description [APP]
6-63
motors including main motor. For mode ‘2’, external
sequence (Refer to APP-26) should be configured.
♦
Abnormal motor can be skipped from running by using
the multi-function input terminals (P1, P2, P3, and P4). If a
multi-function terminal is opened, the inverter stops all
running motors and restarts operation with only normal
motors except the abnormal motor. (Refer to APP-29)
♦
Sleep function is initiated when flow demand is low.
Inverter stops motor when the motor runs below Sleep
Frequency (APP-24) during Sleep Delay Time (APP-23).
While in the sleep state, inverter keeps monitoring and
initiates Wake-Up function when the real value of the
controlling amount has decreased below the Wake-Up
level (APP-25).
☞
Note:
Only one auxiliary motor can be connected with AUX
terminal on control terminal strip without using MMC Option
Board.
[MMC Diagram]
[Draw]:
This is a kind of Open-Loop Tension Control. This
is used to maintain constant tension of material with the
speed difference between main motor and subordinate
motor.
APP-02: Traverse Amplitude
This code sets the frequency amplitude of traverse
operation. The value is the percentage of reference
frequency. The output value is determined by,
Trv. Amp Frequency = (Reference Freq. * Trv. Amp)/100
APP-03: Traverse Scramble Amplitude
This code sets the frequency amplitude of scramble
operation. The output value is determined by,
Trv. Scr Frequency = (Trv. Amp Frequency * (100 - Trv.
Scr))/100
APP-04: Traverse Accel Time
APP-05: Traverse Decel Time
APP
►
Trv. Amp[%]
02 0.0%
0.0
02
Factory Default:
0.0%
0.0
APP
►
Trv. Scr[%]
03 0.0%
0.0
03
Factory Default:
0.0%
0.0
APP
►
Trv Acc Time
04 2.0 sec
2.0
04
Factory Default:
2.0
sec
2.0
APP
►
Trv Dec Time
05 3.0 sec
3.0
05
Factory Default:
3.0
sec
3.0
Related Functions:
APP-08 to APP-31 [MMC Parameters]
DRV-04 [Frequency Mode]
FU2-47 [PID Operation Selection]
I/O-01 to I/O-10 [Analog Signal Input]
EXT 15 to EXT21 [Pulse Input Signal]
I/O-12 to I/O-14 [Multi-Function Input]
EXT-30 to EXT-32 [Multi-Function Output]
Related Functions:
APP-32 to APP-33 [Draw Parameters]
DRV-04 [Frequency Mode]
I/O-01 to I/O-10 [Analog Signal Input]
EXT 06 to EXT-10 [Analog Input Setting]
I/O-12 to I/O-14 [Multi-Function Input]
EXT-02 to EXT-04 [Multi-Function Input]
V1
V2
I
M1
M2
M3
M4
M
ACti
M
Input
Power
Main Motor
Aux. Motor 4
Aux. Motor 3
Aux. Motor 2
Aux. Motor 1
MMC Board
AUX
RLY1
RLY2
RLY3
Summary of Contents for 30 HP30
Page 6: ......
Page 12: ......
Page 16: ...Chapter 1 Installation 1 4 BLANK ...
Page 18: ...Chapter 1 Installation 1 6 BLANK ...
Page 28: ...Chapter 1 Installation 1 16 Notes ...
Page 39: ...Chapter 2 Operation 2 11 Notes ...
Page 40: ......
Page 46: ......
Page 60: ...Chapter 4 Operation Examples 4 14 Notes ...
Page 83: ...Chapter 5 Parameter List 5 23 Notes ...
Page 84: ......
Page 92: ...Chapter 6 Parameter Description DRV 6 8 Notes ...
Page 105: ......
Page 106: ...Chapter 6 Parameter description FU1 6 14 Notes ...
Page 126: ...Chapter 6 Parameter Description FU2 6 34 Notes ...
Page 144: ...Chapter 6 Parameter Description I O 6 52 Notes ...
Page 162: ......
Page 188: ...Chapter 7 Options 7 26 Type 1 Max 400 Watt Type 2 Max 600 Watt A ...
Page 189: ...Chapter 7 Options 7 27 Type 3 ...
Page 194: ......
Page 204: ......
Page 210: ......