Chapter 6 - Parameter Description [I/O]
6-44
[Current]
FM terminal outputs inverter output current. The output
value is determined by,
FM Output Voltage = (Output current / Rated current) ×
10V × IO-41 / 150
[Voltage]
FM terminal outputs inverter output voltage. The output
value is determined by,
FM Output Voltage = (Output voltage / Max. output
voltage) × 10V × IO-41 / 100
[DC link vtg]
FM terminal outputs the DC link voltage of inverter. The
output value is determined by,
FM Output Voltage = (DC link voltage / Max. DC link
voltage) × 10V × IO-41 / 100
[FM Output (FM-CM terminal)]
[Torque]
FM terminal outputs the torque of inverter. The output
value is determined by
FM Output Voltage = (Torque current / Max.Torque
current) × 10V × IO-41 / 150
Note : 1. Max output voltage : 200V class -> 220V
400V class -> 440V
2. Max DC link voltage : 200V class -> 400V
400V class -> 800V
3. Refer to chapter 2 Specification for inverter rated current.
I/O-42: FDT (Frequency Detection) Level
I/O-43: FDT Bandwidth
These functions are used in I/O-44 [Multi-function Auxiliary
Contact Output]. See [FDT-#] in I/O-44.
I/O-44: Multi-function Auxiliary Contact Output
define (AXA-AXC)
The auxiliary contact works (Close) when the defined
condition has occurred.
Setting Range
LCD 7-Seg
Description
FDT-1
0
Output frequency arrival detection
FDT-2
1
Specific frequency level detection
FDT-3
2
Frequency detection with pulse
FDT-4
3
Frequency detection with contact
closure
FDT-5
4
Frequency detection with contact
closure (inverted FDT-4)
OL
5
Overload detection
IOL
6
Inverter overload detection
Stall
7
Stall prevention mode detection
OV
8
Over voltage detection
LV
9
Low voltage detection
OH
10
Overheat detection
I/O
►
FDT freq
42 30.00 Hz
30.00
42
Factory Default:
30.00 Hz
30.00
I/O
►
FDT band
43 10.00 Hz
10.00
43
Factory Default:
10.00
Hz
10.00
Related Functions:
I/O-44 [Multi-function Auxiliary Output]
I/O
►
Aux mode
44 Run
Factory Default:
Run
12
FM Terminal Output
Time
15Vpeak
Avg. 0~10V
500Hz, 2msec (fixed)
12
44
I/O-40
10
V
0 %
100
I/O-41 * 10 V
FM-5G
Output V
Summary of Contents for 30 HP30
Page 6: ......
Page 12: ......
Page 16: ...Chapter 1 Installation 1 4 BLANK ...
Page 18: ...Chapter 1 Installation 1 6 BLANK ...
Page 28: ...Chapter 1 Installation 1 16 Notes ...
Page 39: ...Chapter 2 Operation 2 11 Notes ...
Page 40: ......
Page 46: ......
Page 60: ...Chapter 4 Operation Examples 4 14 Notes ...
Page 83: ...Chapter 5 Parameter List 5 23 Notes ...
Page 84: ......
Page 92: ...Chapter 6 Parameter Description DRV 6 8 Notes ...
Page 105: ......
Page 106: ...Chapter 6 Parameter description FU1 6 14 Notes ...
Page 126: ...Chapter 6 Parameter Description FU2 6 34 Notes ...
Page 144: ...Chapter 6 Parameter Description I O 6 52 Notes ...
Page 162: ......
Page 188: ...Chapter 7 Options 7 26 Type 1 Max 400 Watt Type 2 Max 600 Watt A ...
Page 189: ...Chapter 7 Options 7 27 Type 3 ...
Page 194: ......
Page 204: ......
Page 210: ......