Chapter 6 - Parameter description [FU1]
6-17
FU1-38: Output Voltage Adjustment
This function is used to adjust the output voltage of the
inverter. This is useful when using a motor with a lower
rated voltage than the main input voltage. When this is set
at 100%, inverter outputs its rated voltage.
☞
Note:
The inverter output voltage does not
exceed the main input voltage, even though FU1-
38 is set at 110%.
FU1-39: Energy Save Level
This function is used to reduce the output voltage in
applications that do not require high torque and current at
its steady speed. The inverter reduces its output voltage
after accelerating to the reference frequency (steady
speed) if the energy save level is set at 20%. This function
may cause over-current trip due to the lack of output
torque in a fluctuating load.
This function does not work with 0% set point value.
[When Energy Save Level is set at 20%]
☞
Note:
This function is not recommended for a large load or
for an application that need frequent acceleration and
deceleration.
☞
Note:
This function does not work when ‘Sensorless’ is
selected in FU2-40 [Control Mode].
FU1-50: Electronic Thermal (Motor i
2
t) Selection
FU1-51: Electronic Thermal Level for 1 Minute
FU1-52: Electronic Thermal Level for Continuous
FU1-53: Electronic Thermal Characteristic (Motor
type) selection
These functions are to protect the motor from overheating
without using additional thermal overload relay. Inverter
calculates the temperature rising of the motor using
several parameters and determines whether or not the
motor is overheated. Inverter will turn off its output and
display a trip message when the electronic thermal feature
is activated.
This function activates the ETH parameters by setting
‘Yes’.
This is the reference current when the inverter determines
Related Functions:
FU1-21 [Base Frequency]
FU1-22 [Starting Frequency]
FU1-29
[Volts/Hz
Pattern]
FU1
►
Volt control
38 100.0 %
100
38
Factory Default:
100.0 %
100
Output Voltage
Output
Frequency
FU1-21 [Base Freq]
100%
50%
When set at 50%
FU1
►
Energy save
39 0 %
0
39
Factory Default:
0 %
0
Output Voltage
Output
Frequency
Reference Frequency
(Steady Speed)
100%
80%
FU1
►
ETH select
50 --- No ---
0
50
Factory Default:
No
0
FU1
►
ETH 1min
51 150 %
150
51
Factory Default:
150 %
150
Summary of Contents for 30 HP30
Page 6: ......
Page 12: ......
Page 16: ...Chapter 1 Installation 1 4 BLANK ...
Page 18: ...Chapter 1 Installation 1 6 BLANK ...
Page 28: ...Chapter 1 Installation 1 16 Notes ...
Page 39: ...Chapter 2 Operation 2 11 Notes ...
Page 40: ......
Page 46: ......
Page 60: ...Chapter 4 Operation Examples 4 14 Notes ...
Page 83: ...Chapter 5 Parameter List 5 23 Notes ...
Page 84: ......
Page 92: ...Chapter 6 Parameter Description DRV 6 8 Notes ...
Page 105: ......
Page 106: ...Chapter 6 Parameter description FU1 6 14 Notes ...
Page 126: ...Chapter 6 Parameter Description FU2 6 34 Notes ...
Page 144: ...Chapter 6 Parameter Description I O 6 52 Notes ...
Page 162: ......
Page 188: ...Chapter 7 Options 7 26 Type 1 Max 400 Watt Type 2 Max 600 Watt A ...
Page 189: ...Chapter 7 Options 7 27 Type 3 ...
Page 194: ......
Page 204: ......
Page 210: ......