Chapter 6 - Parameter Description [DRV]
6-3
DRV-02: Deceleration Time
The inverter targets the FU2-70 when accelerating or
decelerating. When the FU2-70 is set to “Maximum
Frequency”, the acceleration time is the time taken by the
motor to reach FU1-20 from 0 Hz. The deceleration time is
the time taken by the motor to reach 0 Hz from FU1-20
[Maximum Frequency].
When the FU2-70 is set to ‘Delta Frequency’, the
acceleration and deceleration time is the time taken to
reach a targeted frequency (instead the maximum
frequency) from a frequency.
The acceleration and deceleration time can be changed to
a preset transient time via multi-function inputs. By setting
the multi-function inputs (P1, P2, P3) to ‘XCEL-L’, ‘XCEL-
M’, ‘XCEL-H’ respectively, the Accel and Decel time set in
I/O-25 to I/O-38 are applied according to the binary inputs
of the P1, P2, P3.
➨
Note:
I/O-12 to I/O-14: Sets the terminal function of P1, P2,
P3 terminal inputs.
Code
LCD
display
Description
XCEL-
H
XCEL-
M
XCEL-
L
Factory
setting
DRV-
01
Acc time
Acc time 0
0
0
0
10 sec
DRV-
02
Dec time
Dec time 0
0
0
0
20 sec
I/O-25 ACC-1
Acc time 1
0
0
1
20 sec
I/O-26 DEC-1
Dec time 1
0
0
1
20 sec
I/O-27 ACC-2
Acc time 2
0
1
0
30 sec
I/O-28 DEC-2
Dec time 2
0
1
0
30 sec
I/O-29 ACC-3
Acc time 3
0
1
1
40 sec
I/O-30 DEC-3
Dec time 3
0
1
1
40 sec
I/O-31 ACC-4
Acc time 4
1
0
0
50 sec
I/O-32 DEC-4
Dec time 4
1
0
0
50 sec
I/O-33 ACC-5
Acc time 5
1
0
1
40 sec
I/O-34 DEC-5
Dec time 5
1
0
1
40 sec
I/O-35 ACC-6
Acc time 6
1
1
0
30 sec
I/O-36 DEC-6
Dec time 6
1
1
0
30 sec
I/O-37 ACC-7
Acc time 7
1
1
1
20 sec
I/O-38 DEC-7
Dec time 7
1
1
1
20 sec
FU2-71 [Accel/Decel time scale]
Set the Accel / Decel time unit.
Setting
Unit
Description
0 0.01
sec
Minimum 0 sec settable
Maximum 60 sec settable
1 0.1
sec
Minimum 0 sec settable
Maximum 600 sec settable
(Factory setting)
2 1
sec
Minimum 0 sec settable
Maximum 6000 sec settable*
* Up to 6000 sec setting is avaiable via LE-200 keypad.
DRV-03: Drive Mode (Run/Stop Method)
Select the source of run/stop command.
DRV
►
Dec. time
02 20.0 sec
20.0
02
Factory Default:
20.0 sec
20.0
Related Functions:
FU1-20 [Max freq]
FU2-70 [Reference freq. for Accel/Decel]
FU2-71 [Accel/Decel time scale]
I/O-12 to I/O-14 [Multi-function input
terminal P1, P2, P3]
I/O-25 to I/O-38 [Acc/Dec time for step
frequency]
FU2-70: Selects the frequency to be targeted for acceleration
and deceleration. [Max Freq, Delta Freq]
FU2-71: Selects the time scale. [0.01, 0.2, 1]
I/O-12 to I/O-14: Sets the terminal function of P1, P2, P3
terminal inputs.
I/O-25 to I/O-38: Presets the Accel/Decel time activated via
multifunction inputs (P1, P2, P3)
Output Frequency
Max. Freq.
Time
Acc. time
Dec. time
DRV
►
Drive mode
03 Keypad
1
03
Factory Default:
Fx/Rx-1
1
Summary of Contents for 30 HP30
Page 6: ......
Page 12: ......
Page 16: ...Chapter 1 Installation 1 4 BLANK ...
Page 18: ...Chapter 1 Installation 1 6 BLANK ...
Page 28: ...Chapter 1 Installation 1 16 Notes ...
Page 39: ...Chapter 2 Operation 2 11 Notes ...
Page 40: ......
Page 46: ......
Page 60: ...Chapter 4 Operation Examples 4 14 Notes ...
Page 83: ...Chapter 5 Parameter List 5 23 Notes ...
Page 84: ......
Page 92: ...Chapter 6 Parameter Description DRV 6 8 Notes ...
Page 105: ......
Page 106: ...Chapter 6 Parameter description FU1 6 14 Notes ...
Page 126: ...Chapter 6 Parameter Description FU2 6 34 Notes ...
Page 144: ...Chapter 6 Parameter Description I O 6 52 Notes ...
Page 162: ......
Page 188: ...Chapter 7 Options 7 26 Type 1 Max 400 Watt Type 2 Max 600 Watt A ...
Page 189: ...Chapter 7 Options 7 27 Type 3 ...
Page 194: ......
Page 204: ......
Page 210: ......