12-16
Diagnostic Message Descriptions
ECODRIVE03-FL*-04VRS
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
F407 Error during initialization of master communication
An error occurred during initialization and verification of command
communications card (DIO1.1/PBK2).
Cause:
•
No command communications card is inserted
•
Wrong command communications card is inserted
•
Wrong Firmware is loaded
Remedy:
•
Insert correct command communications card
•
Replace
Firmware
F408 Fatal error of the interface card
Communication with the DIO1.1 parallel interface card of the DKC21.3
respectively with the Profibus interface card of the DKC03.3 has been
disrupted.
Cause:
•
DIO/PBK2 Card not properly seated
•
Impermissible memory access occurs.
Remedy:
•
Check card seating
•
Switch unit off and on. If error still pending, replace hardware.
F411 Double SST failure shutdown
Description:
The EcoX master cyclically sends the synchronization and command
value telegram (SST). If it fails for 2 cycles, warning E411 is generated.
The cycle time for the SST is 500 µs. If controller enable has been set
and the SST fails for 2 cycles, error F411 is generated instead of warning
E411.
Cause:
1. The EcoX master has been switched to phase 2
2. The EcoX bus has not been correctly wired
3. The EcoX bus is disturbed
4. The EcoX bus has not been parameterized in the EcoX master
5. The supply voltage of the EcoX master has been cut off
Remedy for...:
1. Switch EcoX master to phase 3 or phase 4
2. Check the wiring of the EcoX bus
3. Check the EcoX bus
4. Check
parameterization
5. Check supply voltage of the EcoX master
Summary of Contents for Rexroth OptiFeed-FS EcoDrive 03 FLP04VRS
Page 18: ...XVI Table of Contents ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P ...
Page 348: ...11 18 Command Communications ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P Notes ...
Page 418: ...13 4 Connectors ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P Notes ...
Page 470: ...16 4 IDS Accessories ECODRIVE03 FL 04VRS DOK ECODR3 FL 04VRS FK01 EN P Notes ...
Page 489: ......