ECODRIVE03-FL*-04VRS
EMD Module (EcoX-Bus)
15-17
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
The positive connection of a load must be connected to the gray
connection clamp and the negative connection must be connected to the
blue connection clamp.
ap5374f1_AE.WMF
Fig. 15-17: Connection of the Actuators
Fieldbus Connectors
Note:
For the first and the last unit along an EcoX bus, a bus
terminationmust be attached to the end of the conductor. The
IKB0036 (Connection between Input/Output Module and drive
controller) and IKB0037 (Connection from Input/Output
Modules) cable assemblies have an integrated bus termination
in the connectors.
Connection Between Input/Output Module and Drive Controller
The fieldbus input/output modules (EMD Module) are galvanically isolated
from each other.
The input/output module must be connected to the drive controller. On the
EMD side, a 9-pole D-Sub connector with a maximum housing width of
16 mm and a twisted conductor with a diameter of 0.25 mm
2
must be
used. The maximum allowed cable length is 2 m.
Note:
A pre-assembled cable IKB0036 is provided for the connection
between Input/Output module and drive controller.