ECODRIVE03-FL*-04VRS
Functions
8-21
DOK-ECODR3-FL*-04VRS**-FK01-EN-P
Task 3 is also enabled in Parameter AA00, as is the start instruction.
Program execution of Task 3 begins automatically immediately after
power-up (even in Manual Mode).
Task 3 is deactivated only in Parameter Mode. Task 3 continues to run in
the event of a fault or emergency stop.
Lockouts can therefore also be monitored via this cycle.
Note:
Axis movements may not be processed in Task 3.
Example:
Input in Parameter AA00
AA00
0000 0800 1
Input in the programming instruction
0800 AKN
I0.00.7 1
0801 APE
Q0.00 00000000
0802 WAI
02.000
0803 AEA
Q0.00.4 1
0804 AKN
I0.00.6 1
0805 AEA
Q0.00.4 0
0806 AEA
Q0.00.6 1
0807 WAI
00.100
0808 AEA
Q0.00.6 0
0809 JMP
0802
Note:
Task 1 and 2 are equivalent. Within the NC cycle, the task are
completed in numerical order (1, 2, 3).
Task 3